| Date |
Text |
| 2009-07-15 12:15:59 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SHOW DIMENSIONS ON ELECTRICAL SITE |
| | PLANS FOR CLEARANCES FROM HOUSE. THE LOCATIONS ARE |
| | NOTED HOWEVER SITE/SURVEY FINAL PLANS NEED TO SHOW A |
| | RECORD OF THE EXACT LOCATION UNIT WILL BE PLACED. |
| | 110.26, NFPA_37 |
| | |
| | 2) NOTE: PLAN SUBMITTED FOR SLAB DETAIL IS A PHOTO-COPY |
| | OF AN ENGINEER PLAN. PLEASE KNOW THAT THE TITLE BLOCK, |
| | SIGNATURE, DATE AND SEAL WOULD BE REQUIRED FROM THAT |
| | ENGINEER WHEN USING THEIR PLAN OR DETAIL. FS |
| | 471.025,FAC 61G15-23.002 |
| | WHEN MEETING EXCEPTIONS DESIGN MAY BE UNDER FS 489. |
| | |
| | 3) NOTE: PLEASE SHOW OR PROVIDE INFORMATION OF THE LOAD |
| | SHEDDING OF HEAT STRIPS ON THE STAND-BY SYSTEM. PLANS |
| | STATE THE ASSUMED LOAD FOR A/C CONDENSING UNITS, |
| | HOWEVER IF AUTOMATIC TRANSFER IS TAKING PLACE. THE LOAD |
| | FOR HEAT MUST ALSO BE FIGURED UNLESS LOAD SHEDDING. |
| | 702.5 |
| | PLANS DO MENTION LOAD SHEDDING OF NON-ESSENTIAL LOADS |
| | HOWEVER UNCLEAR HOW HEAT ON A/C SYSTEM IS UNDER THIS. |
| | |
| | 4) NOTE: WHEN MEETING 702.11 THEN SIGNAGE IS REQUIRED |
| | AT THE SERVICE LOCATION AS WELL AS MAIN HOUSE SERVICE |
| | LOCATION AS TO THE DISCONNECTING MEANS FOR THE STAND-BY |
| | POWER. |
| | 225.37, 230.2E |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |