| 2009-07-14 17:02:16 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- A) FLAT ROOF ASSEMBLY SELECTED ON SHEET 26 OF 38 OF | | | NOA 08-0410.09 SUBMITTED IS LIMITED BY GENERAL | | | LIMITATION #9 AND THE MAXIMUM DESIGN PRESSURE IS | | | -45PSF. GENERAL LIMITATION #9 DOESN'T ALLOW NAIL | | | ENHANCING. SEE GENERAL LIMITATION #9 ON LAST PAGE OF | | | NOA. THIS ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES | | | FOR PERIMETER AND CORNER AREAS OF THIS BUILDING. | | | | | | B) NEED TO SELECT ANOTHER ASSEMBLY THAT IS LIMITED BY | | | GENERAL LIMITATION #7 AND PROVIDE CORRESPONDING RAS 117 | | | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER | | | AREAS. | | | | | | C) RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED BY | | | ANY OF THE PROFESSIONALS LISTED ON GENERAL LIMITATION | | | #7 OF NOA SUBMITTED. DESIGN PROFESSIONAL TO TAKE INTO | | | CONSIDERATION THAT BUILDING IS LOCATED ON EXPOSURE "C" | | | AS REQUIRED BY 2009 REVISIONS TO THE 2007 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|