| Notes |
| Date |
Text |
| 2009-10-08 07:57:30 | **PROVISO** | | | | | | 1. RETURN AIR TRANSFER DUCT AT OFFICE NOT SIZED TO MEET | | | BALANCED RETURN EXCEPTIONS UNDER FBC-M 601.4. A FIELD | | | TEST WILL BE REQUIRED AT FINAL INSPECTION TO CHECK FOR | | | PRESSURE DIFFERENTIAL OF 0.01 INCHES WC OR LESS PER | | | FBC-M 601.4. | | | | | | 2. PROVIDE DOCUMENTATION TO FIELD INSPECTOR | | | DEMONSTRATING A MATCHED SYSTEM BETWEEN THE NEW AHU AND | | | THE EXISTING CU IN ACCORDANCE WITH FBC-B 13-101.6. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|