| Plan Review Notes For Permit 09070208 |
| Permit Number |
09070208 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-08-27 18:27:07 | **REVISION REQUIRED** | | | 1. REVISE PLANS SHOWING MISSING DUCT SIZES AT TRANSFERS | | | FOR BATHROOM AND OFFICE. | | | 2. PROVIDE DOCUMENTATION SHOWING PROPOSED AHU AND | | | CONDENSER COMPRISE A MATCHED SYSTEM IN ACCORDANCE WITH | | | FBC-B 13-101.6. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|