| Plan Review Notes For Permit 09070203 |
| Permit Number |
09070203 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-10-02 12:04:13 | ** PROVISO ** | | | | | | 1) NOTE: THE PLANS STATE A 2006 EDITION OF NFPA-70 ( | | | NEC). | | | THE PROJECT IS SUBMITTED UNDER THE 2005 NEC. THE NEXT | | | CODE IN EFFECT WILL BE THE 2008 NEC. | | | | | | 2) NOTE: FOOTER STEEL IS MISSING FROM GROUNDING | | | ELECTRODE SYSTEM. 250.50 PLANS STATE THAT CONCRETE IS | | | FIBER REINFORCED HOWEVER BASED ON STRUCTURAL PLANS | | | THERE ARE 3-#5 BARS IN FOOTERS. | | | | | | 3) NOTE: STORAGE TYPE WATER HEATERS ARE CONTINUOUS LOAD | | | WHICH REQUIRES LOAD TO BE FIGURED AT 125%. | | | | | | 4) NOTE: PLANS STILL INDICATE SMOKE DETECTORS INSTEAD | | | OF SMOKE ALARMS. PLEASE SEE NFPA-72 11.5.1, 11.8.3 | | | | | | 5) NOTE: PLANS/TITLE BLOCKS DO NOT CONTAIN ANY ADDRESS | | | ON TITLE BLOCKS. FAC 61G1-16.004. FBC 106.5 FOR RECORD | | | PLANS. THIS WAS REDLINED ON ELECTRICAL SHEETS. | | | | | | 6) NOTE: WASHER LOAD SHALL BE 1.5/1500VA MINIMUM PER | | | 220.52 | | | | | | ** PLEASE REVISE PLANS BEFORE ROUGH ALONG WITH ANY | | | OTHER REVISIONS. | | | | | | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|