Notes
Date Text
2009-07-23 11:22:05DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 PLUMBING
  
 1. SHT A-2 SANITARY RISER DIAGRAM. THE KITCHEN SINK
 SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT
 FOR THE BATHROOM FIXTURES. SECTION P3108.1.
  
 2. SHT A-2 SANITARY RISER DIAGRAM. THE AUTOMATIC WASH
 MACHINE SHALL CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES IN DIAMETER. SECTION 406.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  