 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES.***BEDROOM #1.
  
 2} 250.50 GROUNDING ELECTRODE SYSTEM
 ALL GROUNDING ELECTRODES AS DESCRIBED IN 250.52(A)(1)
 THROUGH (A)(6) THAT ARE PRESENT AT EACH BUILDING OR
 STRUCTURE SERVED SHALL BE BONDED TOGETHER TO FORM THE
 GROUNDING ELECTRODE SYSTEM. WHERE NONE OF THESE
 GROUNDING ELECTRODES EXIST, ONE OR MORE OF THE
 GROUNDING ELECTRODES SPECIFIED IN 250.52(A)(4) THROUGH
 (A)(7) SHALL BE INSTALLED AND USED.250.52(A)(3)
 CONCRETE-ENCASED ELECTRODE AN ELECTRODE ENCASED BY AT
 LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED WITHIN AND
 NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR FOOTING
 THAT IS IN DIRECT CONTACT WITH THE EARTH, CONSISTING OF
 AT LEAST 6.0 M (20 FT) OF ONE OR MORE BARE OR ZINC
 GALVANIZED OR OTHER ELECTRICALLY CONDUCTIVE COATED
 STEEL REINFORCING BARS OR RODS OF NOT LESS THAN 13 MM (
 1/ 2 IN.) IN DIAMETER, OR CONSISTING OF AT LEAST 6.0 M
 (20 FT) OF BARE COPPER CONDUCTOR NOT SMALLER THAN 4
 AWG. REINFORCING BARS SHALL BE PERMITTED TO BE BONDED
 TOGETHER BY THE USUAL STEEL TIE WIRES OR OTHER
 EFFECTIVE MEANS.
  
 3} KITCHEN COUNTERTOP RECEPTACLES MUST BE GFI PROTECTED
 PER 210.8(A)(6) GFI. INDICATE SAME ON THE PLANS.
  
 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.*** SEE BEDROOM #4
 FOR MISSING SMOKE ALARM.
  
 5} 210.52(H) HALLWAYS IN DWELLING UNITS, HALLWAYS OF
 3.0 M (10 FT) OR MORE IN LENGTH SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET.
 AS USED IN THIS SUBSECTION, THE HALL LENGTH SHALL BE
 CONSIDERED THE LENGTH ALONG THE CENTERLINE OF THE HALL
 WITHOUT PASSING THROUGH A DOORWAY.
  
 NOTE : SEE 230.70 (A)(1) IF THE SERVICE CONDUCTORS DO
 NOT RUN FROM THE METER TO THE PANEL UNDERGROUND, A
 DISCONNECT WOULD BE REQUIRED AT THE METER.
  