| 2009-07-28 16:30:55 | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| | 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR |
| | DEFICIENCIES.***BEDROOM #1. |
| | |
| | 2} 250.50 GROUNDING ELECTRODE SYSTEM |
| | ALL GROUNDING ELECTRODES AS DESCRIBED IN 250.52(A)(1) |
| | THROUGH (A)(6) THAT ARE PRESENT AT EACH BUILDING OR |
| | STRUCTURE SERVED SHALL BE BONDED TOGETHER TO FORM THE |
| | GROUNDING ELECTRODE SYSTEM. WHERE NONE OF THESE |
| | GROUNDING ELECTRODES EXIST, ONE OR MORE OF THE |
| | GROUNDING ELECTRODES SPECIFIED IN 250.52(A)(4) THROUGH |
| | (A)(7) SHALL BE INSTALLED AND USED.250.52(A)(3) |
| | CONCRETE-ENCASED ELECTRODE AN ELECTRODE ENCASED BY AT |
| | LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED WITHIN AND |
| | NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR FOOTING |
| | THAT IS IN DIRECT CONTACT WITH THE EARTH, CONSISTING OF |
| | AT LEAST 6.0 M (20 FT) OF ONE OR MORE BARE OR ZINC |
| | GALVANIZED OR OTHER ELECTRICALLY CONDUCTIVE COATED |
| | STEEL REINFORCING BARS OR RODS OF NOT LESS THAN 13 MM ( |
| | 1/ 2 IN.) IN DIAMETER, OR CONSISTING OF AT LEAST 6.0 M |
| | (20 FT) OF BARE COPPER CONDUCTOR NOT SMALLER THAN 4 |
| | AWG. REINFORCING BARS SHALL BE PERMITTED TO BE BONDED |
| | TOGETHER BY THE USUAL STEEL TIE WIRES OR OTHER |
| | EFFECTIVE MEANS. |
| | |
| | 3} KITCHEN COUNTERTOP RECEPTACLES MUST BE GFI PROTECTED |
| | PER 210.8(A)(6) GFI. INDICATE SAME ON THE PLANS. |
| | |
| | 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2 |
| | RESIDENTIAL FLORIDA BUILDING CODE.*** SEE BEDROOM #4 |
| | FOR MISSING SMOKE ALARM. |
| | |
| | 5} 210.52(H) HALLWAYS IN DWELLING UNITS, HALLWAYS OF |
| | 3.0 M (10 FT) OR MORE IN LENGTH SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET. |
| | AS USED IN THIS SUBSECTION, THE HALL LENGTH SHALL BE |
| | CONSIDERED THE LENGTH ALONG THE CENTERLINE OF THE HALL |
| | WITHOUT PASSING THROUGH A DOORWAY. |
| | |
| | NOTE : SEE 230.70 (A)(1) IF THE SERVICE CONDUCTORS DO |
| | NOT RUN FROM THE METER TO THE PANEL UNDERGROUND, A |
| | DISCONNECT WOULD BE REQUIRED AT THE METER. |
| | |
| | .IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |