| 2009-07-31 12:52:51 | NEW SF RESIDENCE (R3), BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY FOR IMPACT FEES. |
| | BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT. |
| | |
| | 3- SHEET A-1: PROVIDE DRAINAGE PLAN. SEC. R401.3 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. SHOW ON SITE PLAN |
| | DRAINAGE OF WATER BY USING ARROWS SHOWING DIRECTION OF |
| | WATER. WATER CAN'T BE DIVERTED TO THE NEIGHBOR'S |
| | PROPERTY. |
| | |
| | 4- SHEET A-2: |
| | A) ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO |
| | THE 2007 FLORIDA RESIDENTIAL CODE THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C" NOT "B". REVISE DESIGN DATA |
| | NOTE #7 AND WIND DESIGN INFORMATION. ALSO, REVISE ALL |
| | DESIGN PRESSURES FOR COMPONENTS AND CLADDING. |
| | |
| | B) PROVIDE AREA TABULATIONS. EX: A/C AREA, STORAGE, |
| | PORCH TO PROPERLY ASSESS RADON AND BUILDING VALUATION |
| | SEC. 108.3 CITY AMENDMENTS TO FBC. |
| | |
| | 5- SHEET A-3: |
| | A) PROVIDE DOOR AND WINDOW SCHEDULE OR SPECIFY SIZE OF |
| | DOORS/WINDOWS ON FLOOR PLAN TO VERIFY COMPLIANCE WITH |
| | THE EGRESS REQUIREMENTS OF SEC. R310 AND R311. AND TO |
| | VERIFY COMPLIANCE WITH BATHROOM DOOR MIN. SIZE. |
| | |
| | B) REVISE DOORS AND WINDOWS DESIGN PRESSURES. |
| | COORDINATE WITH ITEM #4 ABOVE. |
| | |
| | 6- SHEET A-4: |
| | A) REVISE ROOF SHEATHING NOTES SHOWN ON THE WALL |
| | SECTIONS. NEED TO USE MIN. 8D RING SHANK NAILS AND THEY |
| | NEED TO BE MIN. 4"O.C. ON ROOF ZONE 3. AS REQUIRED BY |
| | SEC. R803.2.3.1 AND FIGURE R803.2.3.1 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | B) FRONT ELEVATION DOESN'T MATCH FLOOR PLAN. |
| | |
| | C) COORDINATE SPECIFICATIONS SHOWN ON WALL SECTIONS FOR |
| | WALL TO ROOF TRUSS ATTACHMENT TO MATCH ROOF FRAMING |
| | PLAN SPECIFICATIONS. |
| | |
| | D) PROVIDE COMPLETE SPECIFICATIONS ON WALL SECTIONS FOR |
| | ATTIC VENTILATION TO SHOW COMPLIANCE WITH SEC. R806. |
| | SPECIFY SIZE AND LOCATION OF VENTS. |
| | |
| | E) REVISE INSULATION VALUE SHOWN ON WALL SECTION TO |
| | MATCH ENERGY CALCULATIONS. ALSO, R19 DOESN'T FIT ON 2X4 |
| | WALL. REVISE AS REQUIRED. |
| | |
| | F) SEC. 8/A-4: SPECIFY STUCCO THICKNESS AS REQUIRED BY |
| | SE TABLE R702.1(1) OF 2007 FLORIDA RESIDENTIAL CODE. |
| | ALSO, REQUIRES 2 LAYERS OF VAPOR BARRIER AS REQUIRED BY |
| | SEC. R703.6.3. |
| | |
| | G) SECTION 7/A-4: PROVIDE DETAIL/SPECIFICATIONS FOR |
| | PREPARATION OF OPENINGS TO RECEIVE STORM SHUTTERS. |
| | |
| | H) SEC. 9/A-4: SPECIFY LOCATION OF VENTS. SEC. R806 |
| | 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK |
| | SPECIFIC MULLION SIZE TO VERIFY COMPLIANCE WITH THE |
| | CALCULATED DESIGN PRESSURES. |
| | |
| | B) SINGLE HUNG WINDOWS: NEED TO PROVIDE CURRENT FLORIDA |
| | PRODUCT APPROVAL FL4065-R5 AND CORRESPONDING DRAWINGS. |
| | PRODUCT APPROVAL SUBMITTED FL4065.1 R3 IS NOT THE MOST |
| | CURRENT ONE. |
| | |
| | 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 9- ENERGY CALCULATIONS SUBMITTED. |
| | A) COMPLETE ALL THE INFORMATION ON TOP OF FORM |
| | INCLUDING THE SPECIFIC ADDRESS WHEN APPLYING FOR |
| | PERMIT. |
| | |
| | B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM TO |
| | CERTIFY COMPLIANCE WITH THE CODE. |
| | |
| | C) COMPLETE ALL THE INFORMATION ON THE CODE COMPLIANCE |
| | CHECKLIST PAGE. NOTHING WAS CHECKED. |
| | |
| | 10- STORM SHUTTERS: PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE. AND, CLEARLY MARK ON |
| | SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS (EX; |
| | WALL MOUNTED, BUILT OUT, ETC) AND SPECIFIC ANCHOR TYPE |
| | AND SPACING TO BE USED TO VERIFY COMPLIANCE WITH THE |
| | CALCULATED DESIGN PRESSURES OF SEC. R301 OF 2007 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |