Plan Review Notes
Plan Review Notes For Permit 09070203
Permit Number 09070203
Review Stop B
Sequence Number 1
Notes
Date Text
2009-07-31 12:52:51NEW SF RESIDENCE (R3), BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- BRING PLANS TO PALM BEACH COUNTY FOR IMPACT FEES.
 BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT.
  
 3- SHEET A-1: PROVIDE DRAINAGE PLAN. SEC. R401.3 OF
 2007 FLORIDA RESIDENTIAL CODE. SHOW ON SITE PLAN
 DRAINAGE OF WATER BY USING ARROWS SHOWING DIRECTION OF
 WATER. WATER CAN'T BE DIVERTED TO THE NEIGHBOR'S
 PROPERTY.
  
 4- SHEET A-2:
 A) ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO
 THE 2007 FLORIDA RESIDENTIAL CODE THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT "B". REVISE DESIGN DATA
 NOTE #7 AND WIND DESIGN INFORMATION. ALSO, REVISE ALL
 DESIGN PRESSURES FOR COMPONENTS AND CLADDING.
  
 B) PROVIDE AREA TABULATIONS. EX: A/C AREA, STORAGE,
 PORCH TO PROPERLY ASSESS RADON AND BUILDING VALUATION
 SEC. 108.3 CITY AMENDMENTS TO FBC.
  
 5- SHEET A-3:
 A) PROVIDE DOOR AND WINDOW SCHEDULE OR SPECIFY SIZE OF
 DOORS/WINDOWS ON FLOOR PLAN TO VERIFY COMPLIANCE WITH
 THE EGRESS REQUIREMENTS OF SEC. R310 AND R311. AND TO
 VERIFY COMPLIANCE WITH BATHROOM DOOR MIN. SIZE.
  
 B) REVISE DOORS AND WINDOWS DESIGN PRESSURES.
 COORDINATE WITH ITEM #4 ABOVE.
  
 6- SHEET A-4:
 A) REVISE ROOF SHEATHING NOTES SHOWN ON THE WALL
 SECTIONS. NEED TO USE MIN. 8D RING SHANK NAILS AND THEY
 NEED TO BE MIN. 4"O.C. ON ROOF ZONE 3. AS REQUIRED BY
 SEC. R803.2.3.1 AND FIGURE R803.2.3.1 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 B) FRONT ELEVATION DOESN'T MATCH FLOOR PLAN.
  
 C) COORDINATE SPECIFICATIONS SHOWN ON WALL SECTIONS FOR
 WALL TO ROOF TRUSS ATTACHMENT TO MATCH ROOF FRAMING
 PLAN SPECIFICATIONS.
  
 D) PROVIDE COMPLETE SPECIFICATIONS ON WALL SECTIONS FOR
 ATTIC VENTILATION TO SHOW COMPLIANCE WITH SEC. R806.
 SPECIFY SIZE AND LOCATION OF VENTS.
  
 E) REVISE INSULATION VALUE SHOWN ON WALL SECTION TO
 MATCH ENERGY CALCULATIONS. ALSO, R19 DOESN'T FIT ON 2X4
 WALL. REVISE AS REQUIRED.
  
 F) SEC. 8/A-4: SPECIFY STUCCO THICKNESS AS REQUIRED BY
 SE TABLE R702.1(1) OF 2007 FLORIDA RESIDENTIAL CODE.
 ALSO, REQUIRES 2 LAYERS OF VAPOR BARRIER AS REQUIRED BY
 SEC. R703.6.3.
  
 G) SECTION 7/A-4: PROVIDE DETAIL/SPECIFICATIONS FOR
 PREPARATION OF OPENINGS TO RECEIVE STORM SHUTTERS.
  
 H) SEC. 9/A-4: SPECIFY LOCATION OF VENTS. SEC. R806
 2007 FLORIDA RESIDENTIAL CODE.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 SPECIFIC MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 B) SINGLE HUNG WINDOWS: NEED TO PROVIDE CURRENT FLORIDA
 PRODUCT APPROVAL FL4065-R5 AND CORRESPONDING DRAWINGS.
 PRODUCT APPROVAL SUBMITTED FL4065.1 R3 IS NOT THE MOST
 CURRENT ONE.
  
 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 9- ENERGY CALCULATIONS SUBMITTED.
 A) COMPLETE ALL THE INFORMATION ON TOP OF FORM
 INCLUDING THE SPECIFIC ADDRESS WHEN APPLYING FOR
 PERMIT.
  
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM TO
 CERTIFY COMPLIANCE WITH THE CODE.
  
 C) COMPLETE ALL THE INFORMATION ON THE CODE COMPLIANCE
 CHECKLIST PAGE. NOTHING WAS CHECKED.
  
 10- STORM SHUTTERS: PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE. AND, CLEARLY MARK ON
 SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS (EX;
 WALL MOUNTED, BUILT OUT, ETC) AND SPECIFIC ANCHOR TYPE
 AND SPACING TO BE USED TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES OF SEC. R301 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712