Plan Review Notes
Plan Review Notes For Permit 09070118
Permit Number 09070118
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-28 14:27:20 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} } PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES PER 106.3.5.4 FBC. 215.5 NEC
  
 2} THERE IS AN ATS SHOWN WITH THE SERVICE PANELS ON
 SHEET E3, NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR A
 GENERATOR.THE ATS MAY BE INSTLLED WITH THE SERVICE
 EQUIPMENT BUT SPECS MUST BE PROVIDED WITH THE GENERATOR
 APPLICATION.
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. A
 CONTRACTOR IS SIGNED ON THE PERMIT APPLICATION BUT WAS
 NOT ASSIGNED A PERMIT NUMBER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  