| Plan Review Notes For Permit 09070076 |
| Permit Number |
09070076 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-10-26 13:53:52 | ROOF A/C DUCTWORK INSTALLATION, BUILDING REVIEW | | | CHECKLIST. | | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- ENGINEER DETAIL NEEDS TO CLARIFY IF TAPCONS ARE TO | | | BE ANCHORED TO THE ROOF TRUSSES OR JUST TO ROOF | | | SHEATHING. IF TAPCONS ARE TO BE ATTACHED TO THE ROOF | | | SHEATHING, THEN PROVIDE CALCULATIONS SHOWING HOW THE | | | ROOF SHEATHING ALONE WILL SUPPORT THE DUCTWORK FOR THE | | | SPECIFIED WIND LOADS AS REQUIRED BY SEC. R301 OF 2007 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 2- ENGINEER TO SPECIFY DESIGN CRITERIA, INCLUDING | | | CURRENT BUILDING CODE AND REVISIONS, BUILDING EXPOSURE, | | | WIND LOADING, ETC. | | | ***NOTE: ENGINEER TO TAKE INTO CONSIDERATION THAT | | | ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO THE | | | 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS LOCATED | | | ON EXPOSURE "C". | | | | | | 3- ENGINEER TO PROVIDE COMPLETE SPECIFICATIONS FOR TYPE | | | OF ANGLE OR STRAP TO BE USED. DRAWING ONLY SPECIFY | | | ANGLE OR STRAP. THIS IS NO ENOUGH INFORMATION TO VERIFY | | | IF PROPOSED ANCHORING IS ADEQUATE TO RESIST THE | | | CALCULATED LOADS AS REQUIRED BY SEC. R301 OF 2007 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 4- PROVIDE SPECIFICATIONS FOR TYPE OF DUCTWORK TO BE | | | USED TO RESIST THE CALCULATED DESIGN LOADS OF SEC. R301 | | | OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|