| Plan Review Notes For Permit 09070076 |
| Permit Number |
09070076 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-07-20 11:29:44 | RESIDENTIAL (R3) NEW A/C SYSTEM MECHANICAL REVIEW | | | CHECKLIST. | | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PROVIDE COMPLETE ENERGY CALCULATIONS. ONLY THE FIRST | | | PAGE OF THE CALCULATIONS WERE SUBMITTED. | | | ***NOTE: FORM 1100A-08 SUBMITTED IS THE METHOD A AND | | | REQUIRES ENTIRE HOUSE TO COMPLY WITH CURRENT CODE. FOR | | | NEW A/C SYSTEM ON EXISTING HOUSE THE REQUIRED FORM IS | | | 1100B-08 FOR THE METHOD B AND IT ONLY APPLIES TO THE | | | SPECIFIC SYSTEM TO BE INSTALLED. SEE SEC. N1100.0.8.1 | | | OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 2- PROVIDE A/C SYSTEM COOLING LOAD CALCULATIONS AS | | | REQUIRED BY SEC. N1107.AB.1 OF 2007 FLORIDA RESIDENTIAL | | | CODE. | | | | | | 3- SHOWN ON PLANS LOCATION OF CONDENSER UNIT FOR ZONING | | | REVIEW OF THE SETBACKS. CONTACT ZONING AT 822-1435 OR | | | 805-6720 FOR REQUIREMENTS. | | | | | | 4- CONTRACTOR/INSTALLER TO PROVIDE HIS NAME AND SIGN | | | HIS PLANS AS REQUIRED BY FLORIDA STATUTE SEC. 471.003. | | | | | | 5- PLANS TO SHOW COMPLETE INFORMATION (SEC. 106.1.1 OF | | | CITY AMENDMENTS TO FBC): | | | A) SIZE OF ROOMS AND CFM'S ON EACH ROOM. | | | B) DUCT TYPE AND INSULATION. | | | C) BALANCE RETURN (SEC. M1602.4 OF 2007 FL. RESIDENTIAL | | | CODE). | | | D) BATHROOM EXHAUST FAN. | | | E) CONDENSATE LINES. | | | | | | JULIO GOMEZ | | | PLANS EXAMINER | | | (561)805-6712 |
|