Plan Review Notes
Plan Review Notes For Permit 09070076
Permit Number 09070076
Review Stop M
Sequence Number 1
Notes
Date Text
2009-07-20 11:29:44RESIDENTIAL (R3) NEW A/C SYSTEM MECHANICAL REVIEW
 CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE COMPLETE ENERGY CALCULATIONS. ONLY THE FIRST
 PAGE OF THE CALCULATIONS WERE SUBMITTED.
 ***NOTE: FORM 1100A-08 SUBMITTED IS THE METHOD A AND
 REQUIRES ENTIRE HOUSE TO COMPLY WITH CURRENT CODE. FOR
 NEW A/C SYSTEM ON EXISTING HOUSE THE REQUIRED FORM IS
 1100B-08 FOR THE METHOD B AND IT ONLY APPLIES TO THE
 SPECIFIC SYSTEM TO BE INSTALLED. SEE SEC. N1100.0.8.1
 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE A/C SYSTEM COOLING LOAD CALCULATIONS AS
 REQUIRED BY SEC. N1107.AB.1 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 3- SHOWN ON PLANS LOCATION OF CONDENSER UNIT FOR ZONING
 REVIEW OF THE SETBACKS. CONTACT ZONING AT 822-1435 OR
 805-6720 FOR REQUIREMENTS.
  
 4- CONTRACTOR/INSTALLER TO PROVIDE HIS NAME AND SIGN
 HIS PLANS AS REQUIRED BY FLORIDA STATUTE SEC. 471.003.
  
 5- PLANS TO SHOW COMPLETE INFORMATION (SEC. 106.1.1 OF
 CITY AMENDMENTS TO FBC):
 A) SIZE OF ROOMS AND CFM'S ON EACH ROOM.
 B) DUCT TYPE AND INSULATION.
 C) BALANCE RETURN (SEC. M1602.4 OF 2007 FL. RESIDENTIAL
 CODE).
 D) BATHROOM EXHAUST FAN.
 E) CONDENSATE LINES.
  
 JULIO GOMEZ
 PLANS EXAMINER
 (561)805-6712