| 2009-07-07 10:53:39 | DENIED |
| | REFERENCE: |
| | FBC-2007 RESIDENTIAL |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| | 2007 FUEL GAS CODE. -- THE RISER DIAGRAM SUBMITTED IS |
| | NOT IN ISOMETRIC FORM. (SEE EXAMPLE DRAWN FOR |
| | EXPLAINATION). |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. -- PIPING |
| | MATERIAL FROM METER AND AFTER THE WATER HEATER NOT |
| | INDICATED. |
| | |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE |
| | SEC. G2413.2. |
| | |
| | B. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE |
| | VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR, MATERIALS AND DESIGN. |
| | PER (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT |
| | VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| | STRUCTURAL, ELECTRICAL, GAS, MECHANICAL OR PLUMBING |
| | SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. -- THE COST OF |
| | THE GAS APPLIANCES SHALL BE INCLUDED IN THE VALUATION |
| | OF THE PERMIT. |
| | |
| | C. A LISTED SHUT OFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION |
| | G2420.4. |
| | |
| | D. DRIPS/SEDIMENT TRAPS REQUIRED DOWNSTREAM OF THE |
| | EQUIPMENT SHUT OFF VALVE. SECTION G2419.2/G2419.4. |
| | |
| | E. MANUF. SPEC SHEETS REQUIRED FOR THE REGULATORS. |
| | REGULATORS SHALL BE LISTED AND THE OUTLET BTU CAPACITY |
| | OF THE REGULATOR SHALL BE INDICATED. PLEASE SHOW MODEL |
| | OF REGULATOR BEING INSTALLED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |