| Plan Review Notes For Permit 09070037 |
| Permit Number |
09070037 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-07-07 12:08:47 | *****DENIED***** | | | | | | | | | 1. SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00, | | | THE APPLICANT SHALL FILE WITH THE AHJ PRIOR TO THE | | | FIRST INSPECTION EITHER A CERTIFIED COPY OF THE | | | RECORDED NOTICE OF COMMENCEMENT OR A NOTARIZED | | | STATEMENT THAT THE THE NOTICE HAS BEEN FILED, ALONG | | | WITH A COPY THEREOF. PLEASE BE ADVISED THAT THE | | | REFERENCED MASTER PERMIT NUMBER (08100422) HAS BEEN | | | CLOSED. | | | | | | 2. THE NUMBER OF SPRINKLERS SHOWN IN THE DRAWING IS | | | TWENTY-THREE (23); HOWEVER IN THE TITLE BLOCK OF THE | | | PLAN SHEET INDICATES THAT THERE ARE FORTY-EIGHT (48) | | | TOTAL SPRINKLER ON THIS SHEET AND FORTY-EIGHT (48) | | | TOTAL ON THE JOB. | | | | | | 3. PLEASE ADVISE HOW THE PRINT OF THOMAS J. TWOMEY, | | | P.E. (CONSULTING ENGINEER) IS SHOWN IN THE TITLE | | | WITHOUT HIS SEAL AND SIGNATURE. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|