| 2009-12-09 15:26:04 | BUILDING PLAN REVIEW |
| | PERMIT: 09060761 |
| | ADD: 2400 N FLAGLER DRIVE |
| | CONT: OCEAN GATE G.C. |
| | TEL: (561)644-7446 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REST ROOMS: |
| | 1) BUILDING PROVISO: |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | PLEASE PROVIDE ORIGINAL SIGNED AND SEALED SOILS REPORT. |
| | 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| | POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| | VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| | CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| | SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| | THROUGH 1802.6 . |
| | |
| | 2) BUILDING PROVISO: BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE |
| | AS FOLLOWS: |
| | A) TRUSS ANCHORS |
| | B) GLASS BLOCK |
| | C) LOUVERS |
| | D) EXTERIOR SWING DOORS |
| | E) ROOFING ASSEMBLIES |
| | F) ROOF TOP VENT |
| | |
| | 3) BUILDING PROVISO: WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FOUND ON C1.1 THERE IS A ACCESSIBLE RAMP THAT PROVIDES |
| | ACCESS TO THE RESTROOMS, THE DESIGN INDICATED IS TO THE |
| | FDOT STANDARD, NO SECTIONS ARE PROVIDED FOR THIS ACCESS |
| | RAMP, NO BOTTOM LANDING. THE PLANS SHALL BE DESIGNED TO |
| | THE FLORIDA BUILDING CODE CHAPTER 11, SECTION 8.1 |
| | THROUGH 8.8. THERE ARE NO DETAILS FOUND ON ANY |
| | ARCHITECTURAL PLANS. |
| | |
| | BUILDING PROVISO: FLOOD ZONE A5: MIN ELEVATION: 7'-6". |
| | FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED |
| | AFTER MONOLITHIC POUR.. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |