| 2009-07-06 15:11:29 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | FBC-2007 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS DT-1, DT-2, LS-1 THRU LS-4, LD-1, LD-2, LP-1 |
| | THRU LP-5 & IR-1 REQUIRES A FIRM LICENSE NUMBER, |
| | (CERTIFICATE OF AUTHORIZATION), AND PHONE NUMBER IN THE |
| | TITLE BLOCK OF EACH SHEET. ALSO THE DATE THE SIGNATURE |
| | AND SEAL ARE AFFIXED SHALL BE INDICATED ON THE SEAL. |
| | FAC 61G10-11.010(1)(2) & FS 481.219, 481.306. |
| | |
| | 2. SHT EP1.0 WASTE RISER DIAGRAM. THE FITTING |
| | DOWNSTREAM OF THE WATER CLOSETS DOES NOT GUIDE THE |
| | SEWAGE & WASTE IN THE DIRECT OF FLOW AS REQUIRED IN |
| | SECTION 706.3. PLEASE CORRECT RISER DIAGRAM. |
| | |
| | 3. SHT EP1.0 NOTE #1 OF THE WATER RISER. AIR CHAMBERS |
| | ARE NOT APPROVED. PLEASE DELETE FROM NOTE. PDI-WH 201. |
| | |
| | 4. SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE WATER |
| | PIPING. SHOW ALL PIPE SIZES, VALVES ETC. SECTION |
| | 106.3.5.1.3(3)(10)(13). SECTION 601.1. |
| | |
| | 5. ALL SHEETS DESIGNED BY A DESIGN PROFESSIONAL SHALL |
| | BE SIGNED, SEALED AND DATED BY THE DESIGN PROFESSIONAL. |
| | SECTION 106.1. SOME SHEETS ARE NOT SIGNED, SEALED OR |
| | DATED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |