| 2009-11-30 14:28:10 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | |
| | 1. SHT E-2 LOAD CALCULATIONS INDICATE 4 FRYERS, HOT DOG |
| | & NACHO MACHINES ETC. PER SECTION 1003.1 AN INTERCEPTOR |
| | & SEPARATOR MAY BE REQUIRED. PER SECTION 1003.3.1 A |
| | GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVISE |
| | SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES |
| | AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD |
| | PREPARATION AREAS , SUCH AS IN RESTAURANTS, HOTEL |
| | KITCHENS, HOSPITALS, BARS, FACTORY CAFETERIAS AND |
| | CLUBS. FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS, |
| | PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK |
| | STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE |
| | DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS WITH |
| | PRERINSE SINKS. PLEASE SEE TABLES 1003.3.4.1 & |
| | 1003.3.5.1. INFORMATION REQUIRED FOR EACH TABLE SHALL |
| | BE SUBMITTED TO DETERMINE THE REQUIRED |
| | INTERCEPTOR/GREASE REMOVAL DEVISE SIZE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |