| Date |
Text |
| 2009-07-05 11:41:50 | |
| | |
| | |
| | ** DENIED PLANS REVIEW ** |
| | |
| | 1) NOTE: PLANS ARE SUBMITTED ONLY FOR PLAN REVIEW. |
| | PLEASE ALSO SEE THAT THE PERMIT DESCRIPTION STATED ON |
| | THE 4301 S DIXIE HWY PROJECT IS THE SAME FOR CURRIE |
| | PARK. IN FACT THE PHIPPS PARK APPLICATION STATES * |
| | OTHER: PHIPPS PARK RENOVATION* AND IT STATES THERE WILL |
| | BE NEW BOAT TRAILER PARKING FOR THIS LOCATION. PHIPPS |
| | PARK DOES NOT HAVE BOATING FACILITIES. |
| | |
| | THE APPLICATION FOR CURRIE PARK STATES * OTHER: CURRIE |
| | PARK RENOVATIONS*. |
| | IT APPEARS THE DESCRIPTION OF WORK NEEDS TO BE REVISED |
| | AND LOCATIONS COORDINATED. |
| | |
| | EACH APPLICATION DOES NOT NEED TO MENTION THE OTHER |
| | LOCATIONS. THESE ARE SEPARATE PROJECTS WITH SEPARATE |
| | PLANS AND APPLICATIONS. |
| | |
| | |
| | |
| | 2) NOTE: PLEASE KNOW THAT VERIFICATION WITH BUILDING |
| | OFFICIAL WITH RESPECT TO MULTIPLE BUILDINGS ON THE SAME |
| | PERMIT APPLICATION. EXAMPLE WOULD BE THE PRESS BOX AND |
| | PRO-SHOP. THESE ARE SEPARATE BUILDINGS. THESE MAY BE |
| | REQUIRED TO BE UNDER SEPARATE PERMIT APPLICATION EVEN |
| | THOUGH THE SCOPE OF WORK FOR ALL MAY BE ON THE SAME SET |
| | OF PLANS. THIS IS NOT THE DECISION OF THIS PLAN |
| | REVIEWER HOWEVER IT IS NOTED BASED ON OTHER PERMITTING |
| | DONE. |
| | |
| | 3) NOTE: PLANS MAKE NOTE TO A 2008 EDITION OF THE |
| | FLORIDA BUILDING CODE ADMINISTRATIVE CODE. THERE IS NO |
| | 2008 EDITION. |
| | CURRENTLY PER THE BUILDING OFFICIAL, THE CITY OF WEST |
| | PALM BEACH IS STILL UNDER THE 2004 EDITION OF CHAPTER 1 |
| | OF THE FLORIDA BUILDING CODE. NO NEW CHAPTER 1 |
| | ADOPTIONS TO THE 2007 HAVE BEEN MADE TO DATE. |
| | |
| | |
| | 4) NOTE: THE PRESS-BOX LOCATION IS SHOWING THE INCREASE |
| | FROM 150AMP TO 200AMPS YET THERE IS NO EQUIPMENT |
| | GROUNDING CONDUCTOR SHOWN TO THIS LOCATION. THERE IS |
| | ALSO NO SPECIFIC DETAIL FOR GROUNDING ELECTRODE SYSTEM |
| | AT THIS LOCATION. |
| | PIPE FILL ALSO NEEDS TO BE CALCULATED ONCE INFORMATION |
| | IS SUBMITTED. |
| | 250.32,250.50, 250.122 ETC |
| | |
| | 5) NOTE: THERE IS A DISCONNECT SHOWN ON THE WALL OF |
| | CONCESSION AREA WHERE ELECTRICAL EQUIPMENT IS LOCATED. |
| | PER PLANS THIS LOCATION DOES NOT MEET 110.26 AS SOME |
| | SORT OF EQUIPMENT, COUNTER OR OTHER ITEMS ARE SHOWN IN |
| | WORKING CLEARANCE AREA. |
| | |
| | 6) NOTE: ELECTRICAL SHEET E-3 CONTAIN CODE REFERENCES |
| | TO THE 2008 NEC. THE CURRENT ADOPTED EDITION IS THE |
| | 2005 NEC. HOWEVER DEPENDING ON THE PERMIT APPLICATION |
| | DATE FOR ACTUAL PERMIT THIS WILL DETERMINE CODE |
| | REQUIRED. THERE IS CURRENTLY NO SPECIFIC DATE FOR |
| | ADOPTION OF THE 2008 NEC. THE JULY 1ST DATE WAS |
| | CANCELLED BY THE STATE. THE OFFICIAL DATE IS NOT YET |
| | KNOWN. |
| | THE PLANS ALSO STATE THE 2008 NFPA-101. PLEASE SEE FAC |
| | 69A-60.004 AND THE 2009 REVISIONS TO THE 2007 FBC WHICH |
| | BOTH REFERENCE THE 2006 EDITION OF NFPA-101. |
| | THE STATE ADOPTED 2006, NFPA-101 ON DECEMBER 31ST, |
| | 2008. THE FBC ADOPTED ON MARCH 1ST, 2009. |
| | ** FOR INFORMATION: THERE IS NO 2008 EDITION AND NEXT |
| | EDITION WILL BE 2009. |
| | |
| | 7) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS FOR NEW LIGHTING. PLEASE SEE 13-415.AB.5 |
| | FOR PRESCRIPTIVE REQUIREMENTS. ( PRO-SHOP) MAY NOT ADD |
| | NEW IF EXISTING EXCEEDS LEVELS ALREADY PERMITTED. |
| | |
| | *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE |
| | PERMITS. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |