| Plan Review Notes For Permit 09060742 |
| Permit Number |
09060742 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-07-17 16:09:24 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE A6 SHOWS CONDENSER AT REAR OF HOUSE WHILE M1 | | | SHOWS CONDENSERS ON SIDE OF HOUSE. PLEASE CORRELATE | | | PLANS AND SHOW THE CORRECT LOCATION ON SITE PLAN FOR | | | ZONING REVIEW. | | | | | | 2. THE ENERGY CODE COMPLIANCE FORM SUBMITTED IS NO | | | LONGER VALID. THE CORRECT FORM FOR THIS PROJECT IS FORM | | | 1100A-08 AS OF MARCH 1, 2009. PLEASE SUBMIT THE CORRECT | | | COMPLETED FORM TO DEMONSTRATE COMPLIANCE WITH FBC-R | | | CHAPTER 11 | | | | | | 3. PROVIDE COOLING AND HEATING LOAD CALCULATIONS | | | ATTACHED TO THE ENERGY CODE COMPLIANCE FORM IN | | | ACCORDANCE WITH FBC-R SECTION N1107.AB.1 | | | | | | 4. PROVIDE EQUIPMENT SCHEDULE ON PLANS PER FBC-R | | | SECTION M1401.1 | | | | | | 5. DUCT SIZE MISSING ON PLANS FROM AHU TO FIRST | | | DISTRIBUTION BOX. PROVIDE MISSING INFORMATION PER FBC-R | | | SECTION N1110.A.1 | | | | | | 6. CONTRACTOR SHALL PROVIDE SIGNATURE AND LICENSE | | | NUMBER ON PLANS AS DESIGNER OF RECORD. | | | | | | 7. PROVIDE MANUAL D TO SHOW JUSTIFICATION FOR DUCT | | | DESIGN PER FBC-R SECTION N1110.AB.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|