2009-12-02 13:57:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1ST REVIEW FOR STRUCTURAL DETAIL
  
 1. FBC R301.1, ALL PARTS ARE TO BE CONSTRUCTED TO
 SAFELY SUPPORT ALL LOADS. BY WHICH STANDARD IS THIS
 DESIGNED TO? PLANS GIVE A CODE REFERENCE, FBC
 R6023.2(5), WHICH APPEARS TO CONTAIN A TYPO. SEE FBC
 R602.2, 602.3, 301.1.3. THE PRESCRIPTIVE METHODS IN
 R602 ARE FOR WIND SPEEDS OF LESS THAN 100MPH. OTHER
 PRESCRIPTIVE METHODS ARE AVAILABLE, SEE FBC R301.1, OR
 MAY BE ENGINEERED FBC R301.13.
  
 IT IS NOT CLEAR HOW YOU HAVE DETERMINED THAT A SINGLE
 2X4 IS ACCEPTABLE AS A HEADER OVER THE DOOR AND WINDOW,
 AND THAT 24IN OC IS ACCEPTABLE FOR WALL FRAMING
 SPACING.
  
 2. PROVIDE DIMENSIONS FOR THE DOOR AND WINDOWS. THE
 DOOR HEIGHT IS SPECIFIED, BUT NOT THE WIDTH, WINDOWS DO
 NOT HAVE ANY DIMENSIONS.
  
 3. PROVIDE COMPLETE INFORMATION REGARDING THE LUMBER,
 DIMENSION AND GRADE. FBC R301.
  