Plan Review Notes
Plan Review Notes For Permit 09060729
Permit Number 09060729
Review Stop B
Sequence Number 2
Notes
Date Text
2009-09-09 11:13:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE THE NOA PROVIDED, 3" MINIMUM SHUTTER TO GLASS
 SEPARATION REQUIRED.
  
 2. SEE THE NOA, SHUTTER MOUNTING CONNECTION TYPE PER
 PRODUCT APPROVAL SHOULD CORRELATE WITH THE PRODUCT
 APPROVAL, DRAWING PAGE 2 OF 2, THERE ARE THREE
 DIFFREENT METHODS OF INSTALLATION; A, B, C (VERTICAL
 SECTION). AS "B" IS FOR WOOD SUBSTRATE AND THIS JOB IS
 CONCRETE BLOCK, PLEASE INCLUDE EITHER A OR C IN THE
 COLUMN "SHUTTER MOUNTING CONNECTION TYPE" ON THE
 INSTALLATION SCHEDULE.
  
 3. PLEASE NOTE THAT THE MINIMUM EDGE DISTANCE IS 1 1/4"
 FOR VERTICAL SECTION C, BUT IS 2" MINIMUM FOR VERTICAL
 SECTION A.
  
 4. PLEASE CLARIFY, IT IS NOT CLEAR WHAT YOU ARE USING
 FOR A FASTENER. THIS SHOULD BE EITHER A MALE PANELMATE
 (SECTION A) OR TAPCON (SECTION C).
  
 5. A DETAILED LETTER WAS PROVIDED EXPLAINING HOW THE
 INSTALLATION WOULD BE PERFORMED. THE LETTER DOES NOT
 COMPLY WITH THE REQUIREMENTS OF THE PRODUCT APPROVAL.
 THE PRODUCT APPROVAL PROVIDED DOES NOT INCLUDE
 INSTALLATION USING HURRICANE SHUTTER TRACKS; THIS
 APPEARS TO BE DIRECT MOUNT ONLY. EITHER PROVIDE
 ENGINEERING TO SHOW COMPLIANCE WITH WIND DESIGN
 PRESSURES FOR ALTERNATE METHODS OF INSTALLATION, OR
 REVISE THE INSTALLATION SCHEDULE AND INSTALL THE
 PRODUCT AS DICTATED IN THE PRODUCT APPROVAL.
  
 THE MANUFACTURER MAY HAVE OTHER PRODUCT APPROVALS WHICH
 INCLUDE OTHER METHODS OF INSTALLATION.