| 2009-06-26 16:55:14 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. |
| | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- CLEARLY MARK ON ROOF TILE NOA 07-0220.04 SUBMITTED |
| | WHICH FASTENING OPTION IS GOING TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. SEE TABLES 4 AND 5 AND |
| | MARK SPECIFIC FASTENING OPTION. PROVIDE PRODUCT |
| | APPROVAL IF USING ANY TYPE OF ADHESIVE. |
| | |
| | 2- FLAT ROOF PRODUCT APPROVAL NOA 09-0224.01 SUBMITTED. |
| | CLEARLY MARK WHICH APPROVED ASSEMBLY AND BASE SHEET |
| | FASTENING OPTION IS GOING TO BE USED. IF SELECTED |
| | ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7 THEN |
| | PROVIDE RAS 117 CALCULATIONS SIGNED AND SEALED AS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| | SUBMITTED. IF SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #9, THEN IT CAN'T BE USED FOR THIS BUILDING |
| | BECAUSE IT DOESN'T MEET THE DESIGN PRESSURES AND NAIL |
| | ENHANCING IS NOT ALLOWED. |
| | ***NOTE: DESIGN PROFESSIONAL DOING RAS 117 CALCULATIONS |
| | TO HAVE INTO CONSIDERATION THAT ACCORDING TO THE 2009 |
| | REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE THIS |
| | BUILDING IS LOCATED ON EXPOSURE "C". |
| | |
| | 3- HOUSE VALUE IS MORE THAN $300,000. NEED TO COMPLY |
| | WITH THE ROOF TO WALL CONNECTIONS OF SEC. R611.8.1 OF |
| | 2009 REVISIONS TO THE 2007 FLORIDA EXISTING BUILDING |
| | CODE. PROVIDE COMPLETE SPECIFICATIONS PACKAGE SHOWING |
| | COMPLIANCE WITH THIS SECTION. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |