| Plan Review Notes For Permit 09060714 |
| Permit Number |
09060714 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-07-03 10:46:01 | | | | ** DENIED | | | | | | | | | 1) NOTE: NEED LAYOUT OF EQUIPMENT LOCATIONS IN ROOMS | | | AND AREAS. SEE NOTE #3. | | | | | | 2) NOTE: PLEASE INDICATE CONDUCTOR SIZES FOR EQUIPMENT. | | | IS PUMP 120V? EXISTING? NEW? THE PERMIT WHICH WAS | | | PULLED IN OCTOBER DID NOT PROVIDE ELECTRICAL | | | INFORMATION OR VALUE FOR COMPLETE SCOPE. | | | 310.16, FBC 106.1.1, 106.1.2 | | | | | | 3) NOTE: PLANS NEED TO SHOW LOCATIONS AND ALL WIRING | | | METHODS UNDER NEC 500, 500.4,.6,501.5, 505. | | | PLEASE SEE NFPA-50A, AND B. | | | | | | 4) NOTE: PERSON RESPONSIBLE FOR PLANS NEEDS TO PRINT | | | NAME AND SIGN WHEN MEETING EXCEPTIONS TO FS | | | 471.003,481.229. | | | | | | 5) NOTE: VALUE FOR COMPLETE SCOPE OF WORK INCLUDING ALL | | | EQUIPMENT EVEN IF OWNER SUPPLIED NEEDS TO BE INCLUDED. | | | FBC 108.3. AS THE COMPLETED VALUE AND SCOPE WAS NOT | | | PART OF MAIN PERMIT, IT LEAVES ALL PUMP AND WIRING ETC | | | VALUE UNDER ELECTRICAL. THE PERMIT MAY ALSO NEED ONE | | | FOR ANY LINE VOLTAGE EQUIPMENT AS LOW VOLTAGE PERMIT | | | WAS APPLIED. FBC 105.1 IT IS NOT KNOWN AT THIS TIME. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|