Plan Review Notes
Plan Review Notes For Permit 09060712
Permit Number 09060712
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-04 12:58:49** DENIED PLANS REVIEW **
  
 1) NOTE: PLANS NEED TO STATE THE FOLLOWING CODES FOR
 THE RELEVANT SCOPE OF WORK.
 2004 NFPA-780
 2005 NFPA-70
  
 2) NOTE: MAY NOT SUBMIT PHOTO-COPIES OF SIGNED, DATED
 AND SEALED ENGINEERS PLANS.
 PLEASE HAVE PLANS SIGNED, DATED AND SEALED BY THE
 RESPONSIBLE ENGINEER OF RECORD ON PLANS. FS 471.025,
 FAC 61G15-23.002
  
 3) NOTE: PLANS SPECIFICALLY STATE THE ALUMINUM
 CONDUCTORS SHALL NOT CONTACT EARTH. PLEASE SEE NEC
 250.106 AND SHOW DETAILS AND CONDUCTORS FOR
 CONNECTIONS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  