| Plan Review Notes For Permit 09060703 |
| Permit Number |
09060703 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-07-04 10:57:38 | ** DENIED PLANS** | | | | | | 1) NOTE: THE APPLIED SCOPE OF WORK IS NOT CLEAR. THE | | | APPLICATION STATES INTERIOR DEMOLITION ONLY YET THE | | | PLANS SUBMITTED ARE FOR DEMO WORK AND REMODEL WORK. | | | | | | 2) NOTE: PLEASE SHOW LIGHTING FOR EGRESS PER NFPA-101 | | | 7.8, 7.9.2.1,.2.2. NO BATTERY BACK UP FIXTURES SHOWN | | | FOR MINIMUM EGRESS LIGHTING. THIS IS SHOWN FROM AN | | | EXISTING EMERGENCY CIRCUIT WHICH IS OK AS LONG AS THE | | | BUILDING IS NOT OCCUPIED UNDER EMERGENCY POWER. | | | ** PLEASE KEEP IN MIND THE BUILDING SHALL NOT BE | | | OCCUPIED UNDER EMERGENCY POWER. IF OCCUPIED UNDER | | | EMERGENCY POWER AND THE GENERATOR BREAKER IS TRIPPED OR | | | LOST THEN NO EGRESS LIGHTING WOULD BE PROVIDED. THIS | | | COULD LEAVE LIFE SAFETY EGRESS AREAS IN TOTAL DARKNESS. | | | PLEASE BE SURE TO GO OVER THIS WITH BUILDING | | | OWNER/MANAGEMENT. | | | OBTAIN IN WRITING THAT BUILDING SHALL NOT BE OCCUPIED | | | UNDER EMERGENCY POWER. | | | | | | | | | ** SOME ITEMS MAY BE REDLINED AS PROVISO HOWEVER SCOPE | | | IF NOT CLEAR AT THIS TIME. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|