| 2009-07-27 09:49:25 | |
| | ** DENIED REVIEW. ** |
| | |
| | 1) NOTE: THE SEAL USED BY THE ENGINEER ON PLANS IS NO |
| | LONGER VALID IN THE STATE OF FLORIDA. IN FACT THE SEAL |
| | HAS NOT BEEN VALID FOR MANY YEARS. THE RULING UNDER |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001 REQUIRED |
| | ENGINEERS TO UPDATE THEIR SEALS TO NEW REQUIREMENTS. |
| | THIS RULE WAS PASSED IN FEBRUARY OF 2004. THE STATE DID |
| | GRANT AN EXTENSION HOWEVER THE FINAL DATE OF EXTENSION |
| | WAS DECEMBER 31ST 2005. AT THAT TIME THE SEALS WITH THE |
| | WORDING OF *CERTIFICATE* WERE NO LONGER ACCEPTABLE OR |
| | TO BE USED. |
| | THE LICENSE NUMBER ON SAID PLANS IS STILL VALID WITH |
| | THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION. |
| | PLEASE OBTAIN NEW SEAL. PLEASE SIGN, DATE AND SEAL NEW |
| | PLANS UNDER FLORIDA STATUTES 471.025. |
| | |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE SEE THAT THE ELECTRICAL DETAIL/PLAN |
| | SUBMITTED CONTAINS NO DESIGN PROFESSIONAL PER 471, 481 |
| | OR 489. WHEN MEETING EXCEPTIONS TO 471.003 THEN PLANS |
| | MUST STILL BE UNDER THE DESIGN OF A LICENSED CONTRACTOR |
| | PER 489. |
| | |
| | 3) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF |
| | WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, |
| | DESIGN COST, INSTALLATION ETC EVEN IF ANY OF THESE |
| | ITEMS ARE OWNER SUPPLIED. THE APPLIED VALUE FOR THE |
| | COMPLETE SCOPE OF WORK AT $7,000 IS LOW. |
| | FBC 108.3. |
| | PLEASE PROVIDE COPY OF SIGNED CONTRACTS FOR ALL OF THE |
| | ABOVE. |
| | |
| | ** PER BUILDING OFFICIAL. PLANS AND PERMIT APPLICATIONS |
| | ARE NO LONGER RELEASED AND SHALL REMAIN ON FILE. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |