| 2009-08-17 18:16:04 | THE COMMENTS FROM THE PREVIOUS PLAN REVIEW (7/6/09) |
| | HAVE NOT BEEN ADDRESSED. THE SAME COMMENTS HAVE BEEN |
| | REPEATED HERE AGAIN: |
| | |
| | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN (561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2007 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | THE COMMENTS FROM THE PREVIOUS PLAN REVIEW (7/6/09) |
| | WERE NOT BEEN ADDRESSED. THE SAME COMMENTS HAVE BEEN |
| | REPEATED HERE AGAIN: |
| | |
| | 1) FBC 1604.2 ANCHOR BOLTS FOR 25'-0" LIGHT POLE WITH |
| | FIXTURE F3. PLAN SHEET E05, DETAIL 4, SPECIFIES 4 |
| | ANCHOR BOLTS 3/4" DIA. X 32" WHICH IS NOT CORRECT. THE |
| | BOLTS SHOULD BE 4 ANCHOR BOLTS 1" DIA. X 36" AS |
| | SPECIFIED ON THE SUBMITTED AMERON POLE PRODUCTS |
| | DIVISION DRAWING NO. 0905-043 (8.5" X 11" DRAWING |
| | SHEET). AMEND PLAN SHEET E05. |
| | |
| | 2) FBC 1604.2 BOLT CIRCLE DIAMETER FOR ANCHOR BOLTS FOR |
| | 25'-0" LIGHT POLE WITH FIXTURE F3. PLAN SHEET E05, |
| | DETAIL 4, DOES NOT SPECIFY THE BOLT CIRCLE DIAMETER FOR |
| | THE 4 ANCHOR BOLTS. THE BOLT CIRCLE DIAMETER SHOULD BE |
| | 11.5" AS SPECIFIED ON THE SUBMITTED AMERON POLE |
| | PRODUCTS DIVISION DRAWING NO. 0905-043 (8.5" X 11" |
| | DRAWING SHEET). AMEND PLAN SHEET E05. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6652 ROBERT BROWN |
| | E-MAIL: [email protected] |