| Plan Review Notes For Permit 09060640 |
| Permit Number |
09060640 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-11-16 15:39:34 | 2007 FBC W/2009 REVISIONS | | | | | | REVISIONS REQUIRED | | | | | | 1) SUBMIT 2 COPIES OF REVISED WATER HEATER ENCLOSURE | | | DRAWINGS, SPECIFYING ALL OF THE CONNECTORS THAT WILL BE | | | USED TO PROVIDE A CONTINOUS LOAD PATH TO RESIST A 140 | | | MPH WINDLOAD PER FBC R601.2 AND ADDRESSING THE COMMENTS | | | NOTED ON THE APPROVED DRAWINGS. | | | | | | 2) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF | | | COVERINGS AS REQUIRED BY FAC RULE 9B-72. |
|