| Date |
Text |
| 2009-07-24 09:35:29 | |
| | ** DENIED REVIEW. ** |
| | |
| | 1) NOTE: PLEASE SEE FS 553.73. ALL PLANS SUBMITTED FOR |
| | PERMIT ON OR AFTER MARCH 1ST 2009 SHALL BE UNDER THE |
| | FOLLOWING CODES. |
| | 2007 FBC W/ 2009 REVISIONS. |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | |
| | THESE ARE CODES FOR THIS TRADE REVIEWER. |
| | |
| | 2) NOTE: LIGHTING CONTROLS PER FBC 13-415.AB.1,.1.1, |
| | .1.2 ARE NOT MET BY THE USE OF TWO SINGLE POLE |
| | SWITCHES. MUST MEET PRESCRIPTIVE FOR NEW BEING |
| | INSTALLED IN BUILDINGS OVER 5K SQ FT. |
| | |
| | 3) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE |
| | LEVELS FOR NEW SPACE. PLEASE SEE 13-415.AB.5. THE |
| | LIGHTING FIXTURES NEED TO BE SPECIFIC HOWEVER BASED ON |
| | THE FIXTURES SHOWN THE PERMITTED LIGHTING ENERGY USE IS |
| | EXCEEDED. |
| | |
| | 4) NOTE: PLEASE INDICATE THE LOAD CALCULATIONS PER THE |
| | NATIONAL ELECTRICAL CODE. THE CALCULATION METHOD SHOWN |
| | INDICATES A *.3* WATTS PER SQFT. NO LOCATION IN 220.12 |
| | FOR LIGHTING ALONE STATES A .3. PLEASE ALSO KNOW THAT |
| | WHEN A LIGHTING LOAD EXCEEDS THE WATTS PER SQ FT BASED |
| | ON ACTUAL FIXTURE WATTAGE THEN THE FIXTURE WATTAGE MUST |
| | BE USED. |
| | PLEASE SEE 220.44 FOR RECEPTACLE LOADS WHICH MAY NOT BE |
| | FIGURED IN WITH THE LIGHTING LOAD IN OTHER THAT |
| | DWELLING UNITS. |
| | |
| | ** THE LOAD WILL INCREASE. THE PLANS SHOW A TOTAL OF |
| | 11.9WATTS WHICH IS NOT POSSIBLE WHEN THE LAMP IN ONE OF |
| | THE FIXTURES ALONE FAR EXCEEDS 11.9 WATTS. |
| | PLEASE INDICATE CIRCUITING FOR NEW. BRANCH CIRCUIT |
| | SIZE, CONDUCTOR SIZE AND TO THE LOCATION. |
| | 240.4,310.16,408.4 ETC |
| | |
| | FBC 106.1.1,106.1.2, FOR CLARITY AND ADDITIONAL |
| | INFORMATION. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |