Plan Review Notes
Plan Review Notes For Permit 09060612
Permit Number 09060612
Review Stop B
Sequence Number 1
Notes
Date Text
2009-07-17 14:46:30BUILDING PLAN REVIEW
 PERMIT: 09060612
 ADD: 5501 GEORGIA AV.
 CONT: SULLIVAN
 TEL: (561)310-1899
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS, PLEASE UPDATE SHEET
 A-1.
  
 2) PLEASE UPDATE SHEET A-1. 2007 FBC 1609.1.1 & CHAPTER
 35 REFERENECED STANDARDS RECOGNIZES ASCE 7-05 . ALSO
 1603.1.4 WIND DESIGN DATA.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 2.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) PLEASE PROVIDE A SITE PLAN INDICATING THE LOCATION
 OF THE ADDITION TO THE STRUCTURE. ADMINISTATIVE CODE
 106.3.5.1.1.(1) THE SURVEY SUBMITTED APPEARS TO BE FOR
 620 BUNKER RD.
 NOTE THIS ADDITION MAY HAVE ISSUES ONCE THE LOCATION IS
 PROVIDED ON THE SITE PLAN.
  
 4) PLEASE PROVIDE THE TYPE OF BUILDING CONSTRUCTION OF
 THE EXISTING BUILDING AND NEW ADDITION. ADMINISTRATIVE
 CODE 106.3.1.1(3).
  
 5) SHEET A-2 INDICATES THE USE OF 12 INCH DEEP BAR
 JOIST THE PLAN IS NOT CLEAR AS TO HOW THE BAR JOIST ARE
 TO BE ANCHORED TO THE CBS WALL ON THE ONE SIDE NOR THE
 DOUBLE 2X10'S, SECTION A INDICATES THE TRUSS BEARING
 PLATE TO BE DESIGNED BY TRUSS MANUFACTURER.
  
 6) SHEET A-22 DETAIL-B INDICATES THE THICKNESS OF THE
 METAL DECK TO BE 22 GAUGE GAL METAL BUT NO MENTION OF
 THE DECK CONNECTION TO BAR JOIST. THE DECK IS PART OF
 THE MAIN WIND FORCE RESISTING SYSTEM, PLEASE INDICATE
 TYPE OF FASTENING AND FREQUENCY. 106.3.5.1.1(8)
 BUILDING ENVELOPE/ ROOF SYSTEMS.
  
 7) PRODUCT APPROVALS: SUBMITTED WAS A POLYGLASS OVER
 WOOD DECKS 07-0822.10, PLEASE SUBMIT THE CORRECT
 PRODUCT APPROVAL FOR METAL DECK WITH INSULATION. RULE
 9B-72. WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOW ITEMS:
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2& 3__(NOT KNOWN AT THIS TIME) .
  
 NOT KNOWN___ THE SYSTEM PROVIDED STATES LIMITATION# 7,
 SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A
 REVISED
 FASTENER SPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
  
 _NOT KNOWN__ THE SYSTEM PROVIDED INDICATES LIMITATION#
 9, NO ENHANCED FASTENING ALLOWED.
  
 8) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIESR OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 8A) FIXED WINDOWS.
  
 9) FEES DUE OF $3.98 STATE RADON FEES.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  