Plan Review Notes
Plan Review Notes For Permit 09060583
Permit Number 09060583
Review Stop P
Sequence Number 2
Notes
Date Text
2009-08-11 12:50:52DENIED
 REFERENCE:
 FBC-2007 CHAPTER 1
  
 1. SHT P-1 INDICATES RECONNECTING EXISTING SANITARY &
 WATER TO NEW LAV AS SHOWN ON SHT A-2 DETAIL #1, BUT IS
 INDICATED AS "DELETE SINK" IN HAND WRITTEN WORDS. HAND
 WRITTEN CHANGES TO SIGNED, SEALED & DATED PLANS OF A
 DESIGN PROFESSIONAL IS NOT ACCEPTABLE. SECTION 106.1.3.
 ALSO ALL SHEETS SHALL CORRELATE. IF THE SINK IS DELETED
 ON THE PLUMBING FLOOR PLAN, THEN IT SHALL BE DELETED ON
 THE ARCHITECTURAL SHEETS AS WELL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved