2009-07-08 15:22:38REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. IF THE MECHANICAL CONTRACTOR IS ACTING AS THE
 DESIGNER UNDER FS 471.003, THE QUALIFIER SHALL SIGN THE
 PLANS AS THE DESIGNER OF RECORD.
  
 2. THERE IS NO DETERMINATION AS TO WHICH BUILDING OR
 LOCATIONS WITHIN A BUILDING WHERE THESE DAMPERS ARE TO
 BE LOCATED. THE SPECIFIC LOCATION AND INSTALLATION
 DETAILS OF EACH SMOKE DAMPER SHALL BE SHOWN AND
 PROPERLY IDENTIFIED ON THE BUILDING PLANS BY THE
 DESIGNER IN ACCORDANCE WITH FBC-M 607.8.
  
 3. SHOW HOW THESE DAMPERS ARE TO BE ACTUATED IN
 ACCORDANCE WITH FBC-M 607.3.2.1.
  