Plan Review Notes
Plan Review Notes For Permit 09060555
Permit Number 09060555
Review Stop B
Sequence Number 1
Notes
Date Text
2009-07-15 10:53:38RESIDENTIAL (R3)) ROOF, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 ***NOTE: COMMENTS FOR ROOF PERMIT ONLY BECAUSE OF ROOF
 LEAKS. REVIEW OF PROPOSED ADDITION NOT DONE AT THIS
 TIME.
  
 1- CLEARLY INDICATE ON PRODUCT APPROVAL SUBMITTED WHICH
 FLAT ROOF APPROVED ASSEMBLY AND BASE SHEET FASTENING
 OPTION IS GOING TO BE USED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 2- NOA 07-0228.06 SUBMITTED HAS A HANDWRITTEN NOTE
 STATING PAGE 16. PAGE 16 CORRESPONDS TO AN INSULATED
 FLAT ROOF SYSTEM AND IS LIMITED BY GENERAL LIMITATION
 #9. THIS SYSTEM IS GOOD FOR A MAXIMUM DESIGN PRESSURE
 OF -45PSF. GENERAL LIMITATION #9 (SEE SHEET 26 OF 26)
 DOESN'T ALLOW ANY NAIL ENHANCING. THIS ASSEMBLY CAN NOT
 BE USED IN THIS BUILDING BECAUSE IT DOESN'T MEET THE
 DESIGN PRESSURES. THIS BUILDING IS LOCATED ON EXPOSURE
 "C" AND THE DESIGN PRESSURES FOR PERIMETER AND CORNER
 AREAS ARE HIGHER THAN THOSE SPECIFIED ON THE SELECTED
 SYSTEM.
  
 3- SELECT ANOTHER SYSTEM WITH GENERAL LIMITATION #7 AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
 NOTE: DESIGN PROFESSIONAL TO TAKE IN CONSIDERATION THAT
 THIS BUILDING IS LOCATED ON EXPOSURE "C" WHEN PROVIDING
 THE RAS 117 CALCULATIONS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  