Plan Review Notes
Plan Review Notes For Permit 09060519
Permit Number 09060519
Review Stop E
Sequence Number 2
Notes
Date Text
2009-06-29 10:00:49 
 ** DENIED PLANS **
  
 ** SUBMITTED REVISIONS TO CHANGE SCOPE OF WORK TO
 ACCESS CONTROLS NOT A SECURITY SYSTEM.
  
  
 1) NOTE: PLANS NEED TO STATE THE MINIMUM ADOPTED CODES
 FOR DESIGN AND INSTALLATION.
 PLEASE BE SURE THE FOLLOWING MINIMUM ADOPTED CODES ARE
 STATED ON PLANS.
 FBC 2007W/2009 REVISIONS.
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 FBC CHAPTER 35, FAC 69A-60.003,.004. FAC 69A-3.012, FS
 553.73
  
 2) NOTE: PLEASE INCLUDE NOTES AND INFORMATION ON ACCESS
 CONTROLS UNDER NORMAL AND EMERGENCY PER NFPA-101
 CHAPTER 7. PLEASE BE SURE TO SEE ANY COMMENTS FROM FIRE
 MARSHAL REVIEW.
  
 3) NOTE: PLEASE INCLUDE WIRING METHODS AS THE SCOPE OF
 WORK IN A TYPE I BUILDING. PLEASE PROVIDE DETAILS PER
 NEC 300.21.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  