Plan Review Notes
Plan Review Notes For Permit 09060502
Permit Number 09060502
Review Stop M
Sequence Number 1
Notes
Date Text
2009-06-22 15:30:19REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE FORM N1100-B TO DEMONSTRATE ENERGY CODE
 COMPLIANCE IN ACCORDANCE WITH FBC-R SECTION
 N1100.0.8.1.
  
 2. PROVIDE COOLING LOAD CALCULATIONS ATTACHED TO THE
 METHOD B FORM 1100 IN ACCORDANCE WITH FBC-R SECTION
 N1100.7.AB.1.
  
 3. ONE OF THE 3 BEDROOMS DOES NOT SHOW ANY PROVISIONS
 FOR BALANCED RETURN. SHOW HOW BALANCED RETURN IS TO BE
 ACHIEVED IN ACCORDANCE WITH FBC-R SECTION M1602.4.
  
 4. HOW WILL THE A/C SYSTEM BE POWERED? THERE IS NO
 ELECTRICAL PERMIT APPLICATION TO INSTALL THE POWER
 SUPPLY AND DISCONNECTS FOR THIS SYSTEM.
  
 5. A NOTICE OF COMMENCEMENT WILL BE REQUIRED FOR THIS
 WORK TO BE FILED WITH THE COUNTY CLERK'S OFFICE PRIOR
 TO FIRST INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]