| Plan Review Notes For Permit 09060502 |
| Permit Number |
09060502 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-22 15:30:19 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PROVIDE FORM N1100-B TO DEMONSTRATE ENERGY CODE | | | COMPLIANCE IN ACCORDANCE WITH FBC-R SECTION | | | N1100.0.8.1. | | | | | | 2. PROVIDE COOLING LOAD CALCULATIONS ATTACHED TO THE | | | METHOD B FORM 1100 IN ACCORDANCE WITH FBC-R SECTION | | | N1100.7.AB.1. | | | | | | 3. ONE OF THE 3 BEDROOMS DOES NOT SHOW ANY PROVISIONS | | | FOR BALANCED RETURN. SHOW HOW BALANCED RETURN IS TO BE | | | ACHIEVED IN ACCORDANCE WITH FBC-R SECTION M1602.4. | | | | | | 4. HOW WILL THE A/C SYSTEM BE POWERED? THERE IS NO | | | ELECTRICAL PERMIT APPLICATION TO INSTALL THE POWER | | | SUPPLY AND DISCONNECTS FOR THIS SYSTEM. | | | | | | 5. A NOTICE OF COMMENCEMENT WILL BE REQUIRED FOR THIS | | | WORK TO BE FILED WITH THE COUNTY CLERK'S OFFICE PRIOR | | | TO FIRST INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|