 ** PROVISO **
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW STORAGE TYPE OF
 WATER HEATER LOADS SHALL BE FIGURED AT 125%. LOAD
 CALCULATIONS SHOW 125% HOWEVER IT WAS NOT FIGURED INTO
 CALCULATIONS AT THAT RATE.
 4500VA @ 125% IS 5625VA,
  
 2) NOTE: PANEL SCHEDULE SHALL BE SPECIFIC. THE USE OF
 GENERAL LIGHTING/GENERAL RECEPTACLES IS NOT ACCEPTABLE.
 PLEASE SEE NEC 2005 408.4 AND COMMENTARY IN NEC
 HANDBOOK.
  
 ** PLEASE REVISE THE ABOVE ITEMS BEFORE FINAL. IF THERE
 ARE OTHER REVISIONS THEN THEY MUST BE REVISED BEFORE
 ROUGH.
  