| Plan Review Notes For Permit 09060429 |
| Permit Number |
09060429 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2009-10-08 17:56:15 | | | | | | | ** PROVISO ** | | | | | | 1) NOTE: AS NOTED ON PREVIOUS REVIEW STORAGE TYPE OF | | | WATER HEATER LOADS SHALL BE FIGURED AT 125%. LOAD | | | CALCULATIONS SHOW 125% HOWEVER IT WAS NOT FIGURED INTO | | | CALCULATIONS AT THAT RATE. | | | 4500VA @ 125% IS 5625VA, | | | | | | 2) NOTE: PANEL SCHEDULE SHALL BE SPECIFIC. THE USE OF | | | GENERAL LIGHTING/GENERAL RECEPTACLES IS NOT ACCEPTABLE. | | | PLEASE SEE NEC 2005 408.4 AND COMMENTARY IN NEC | | | HANDBOOK. | | | | | | ** PLEASE REVISE THE ABOVE ITEMS BEFORE FINAL. IF THERE | | | ARE OTHER REVISIONS THEN THEY MUST BE REVISED BEFORE | | | ROUGH. | | | | | | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|