| 2009-09-28 09:24:48 | |
| | ** DENIED ** |
| | |
| | ** COMPLETE NEW PLANS SUBMITTED WHICH HAVE NOT BEEN |
| | PREVIOUSLY SUBMITTED OR REVIEWED. |
| | |
| | 1) NOTE: PLANS CONTAIN A NOTE WHICH STATES ALL |
| | ELECTRICAL IS TO BE DONE UNDER THE 2008 NEC. HOWEVER |
| | ALL PERMIT APPLICATIONS SUBMITTED BEFORE OCTOBER 1ST, |
| | 2009 IS UNDER THE 2005 NEC. |
| | |
| | 2) NOTE: PLEASE SEE FBC R313.1, 313.2, 313.2.1 FOR |
| | SMOKE ALARMS WHICH ARE REQUIRED TO BE BROUGHT UP TO |
| | CURRENT CODE. PLEASE SEE NFPA-72 11.5.1 AND 11.8.3 FOR |
| | REQUIRED LOCATIONS. |
| | PLANS ARE MISSING DEVICES. |
| | PLEASE BE SURE TO SEE 11.8.3 AS ALL SMOKE ALARMS WITHIN |
| | 20FT OF COOKING APPLIANCES SHALL MEET SPECIFIC |
| | REQUIREMENTS. ( OUTSIDE MASTER BEDROOM) |
| | |
| | 3) NOTE: PLANS/RISER INDICATES A 150AMP SERVICE YET THE |
| | FEEDERS FROM THE MAIN TO THE PANEL ARE TOO SMALL. |
| | PLEASE SEE 310.16,310.15B6 AS #2 IS NOT RATED FOR |
| | 150AMPS. |
| | |
| | 4) NOTE: PLANS INDICATE ONE A/C SYSTEM WITH 60AMP OVER |
| | CURRENT PROTECTION. HOWEVER THE MECHANICAL PLANS |
| | INDICATE A SYSTEM WITH 8KW HEAT. THIS 60AMP OCP IS TOO |
| | HIGH. 422.13E(3) |
| | ** ELECTRICAL PLANS INDICATE 10KW FOR AHU. PLEASE |
| | CORRELATE BOTH THE ELECTRICAL AND MECHANICAL PLANS. |
| | |
| | 5) NOTE: PLANS ARE MISSING THE REQUIRED SWITCH AND |
| | LIGHTING OUTLET AT FRONT DOOR ENTRANCE/EXIT. |
| | 210.70 |
| | |
| | 6) NOTE: PLANS ARE MISSING DISCONNECTS FOR BOTH THE |
| | CONDENSING UNIT AND AIR HANDLING UNIT PER 440.11, |
| | 440.12. |
| | |
| | PLEASE BE SURE TO SEE 110.26 FOR CLEARANCES. |
| | THE SYMBOL SHOWN ON PLANS IS FOR A 220V OUTLET ONLY. |
| | |
| | 7) NOTE: PLEASE SEE PLANS AS THE DISCONNECT SHOWN ON |
| | RISER IS NOT SHOWN ON PLANS. PLEASE SEE 110.26 FOR |
| | LOCATION. |
| | PANEL SCHEDULE ALSO CONTAINS A NOTE WHICH STATES THE |
| | PANEL ALREADY EXISTS, YET THE PLANS STATE THE PANEL AND |
| | THE MAIN SERVICE IS NEW. |
| | WHICH IS ACCURATE? |
| | |
| | |
| | 8) NOTE: PLEASE SEE 210.52B1 AS ALL CIRCUITS FOR DINING |
| | ROOM RECEPTACLES SHALL BE 20AMP AND #12. PANEL SCHEDULE |
| | DOES NOT DELINEATE BETWEEN LIGHTS OR RECEPTACLES. PANEL |
| | SCHEDULE DOES STATE AFCI PROTECTION WHICH IS NOT |
| | REQUIRED HOWEVER MAY BE INSTALLED. |
| | PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS ALL |
| | ADDITIONAL DEDICATED CIRCUITS ABOVE THE TWO MINIMUM |
| | SMALL APPLIANCE CIRCUITS SHALL BE FIGURED AT 1500VA FOR |
| | EACH. LOAD CALCULATIONS ONLY INDICATE TWO SMALL |
| | APPLIANCES FOR LOADS. |
| | |
| | 9) NOTE: AS NOTED ABOVE IN COMMENTS #8, SEE 210.52B1, |
| | 210.11C1 AND 220.53 FOR ALL SMALL APPLIANCE LOADS AND |
| | ANY DEDICATED DINING ROOM RECEPTACLE CIRCUITS. THE |
| | PANEL SCHEDULE INDICATES 3-SMALL APPLIANCE CIRCUITS |
| | BEFORE ADDING ANY DINING ROOMS. |
| | |
| | 10) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER |
| | HEATERS ARE CONSIDERED CONTINUOUS LOADS. SEE NEC |
| | COMMENTARY AS THE LAST SENTENCE STATES WHEN SIZING FOR |
| | SERVICE AND FEEDERS ALSO. THIS MEANS THE WATER HEATER |
| | 4500VA SHALL BE FIGURED AT 125% INTO LOAD CALCULATIONS. |
| | |
| | 11) NOTE: PLEASE INDICATE AIC RATING FOR MAIN AND PANEL |
| | PER 110.9. |
| | |
| | |
| | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |