Plan Review Notes
Plan Review Notes For Permit 09060429
Permit Number 09060429
Review Stop E
Sequence Number 3
Notes
Date Text
2009-09-28 09:24:48 
 ** DENIED **
  
 ** COMPLETE NEW PLANS SUBMITTED WHICH HAVE NOT BEEN
 PREVIOUSLY SUBMITTED OR REVIEWED.
  
 1) NOTE: PLANS CONTAIN A NOTE WHICH STATES ALL
 ELECTRICAL IS TO BE DONE UNDER THE 2008 NEC. HOWEVER
 ALL PERMIT APPLICATIONS SUBMITTED BEFORE OCTOBER 1ST,
 2009 IS UNDER THE 2005 NEC.
  
 2) NOTE: PLEASE SEE FBC R313.1, 313.2, 313.2.1 FOR
 SMOKE ALARMS WHICH ARE REQUIRED TO BE BROUGHT UP TO
 CURRENT CODE. PLEASE SEE NFPA-72 11.5.1 AND 11.8.3 FOR
 REQUIRED LOCATIONS.
 PLANS ARE MISSING DEVICES.
 PLEASE BE SURE TO SEE 11.8.3 AS ALL SMOKE ALARMS WITHIN
 20FT OF COOKING APPLIANCES SHALL MEET SPECIFIC
 REQUIREMENTS. ( OUTSIDE MASTER BEDROOM)
  
 3) NOTE: PLANS/RISER INDICATES A 150AMP SERVICE YET THE
 FEEDERS FROM THE MAIN TO THE PANEL ARE TOO SMALL.
 PLEASE SEE 310.16,310.15B6 AS #2 IS NOT RATED FOR
 150AMPS.
  
 4) NOTE: PLANS INDICATE ONE A/C SYSTEM WITH 60AMP OVER
 CURRENT PROTECTION. HOWEVER THE MECHANICAL PLANS
 INDICATE A SYSTEM WITH 8KW HEAT. THIS 60AMP OCP IS TOO
 HIGH. 422.13E(3)
 ** ELECTRICAL PLANS INDICATE 10KW FOR AHU. PLEASE
 CORRELATE BOTH THE ELECTRICAL AND MECHANICAL PLANS.
  
 5) NOTE: PLANS ARE MISSING THE REQUIRED SWITCH AND
 LIGHTING OUTLET AT FRONT DOOR ENTRANCE/EXIT.
 210.70
  
 6) NOTE: PLANS ARE MISSING DISCONNECTS FOR BOTH THE
 CONDENSING UNIT AND AIR HANDLING UNIT PER 440.11,
 440.12.
  
 PLEASE BE SURE TO SEE 110.26 FOR CLEARANCES.
 THE SYMBOL SHOWN ON PLANS IS FOR A 220V OUTLET ONLY.
  
 7) NOTE: PLEASE SEE PLANS AS THE DISCONNECT SHOWN ON
 RISER IS NOT SHOWN ON PLANS. PLEASE SEE 110.26 FOR
 LOCATION.
 PANEL SCHEDULE ALSO CONTAINS A NOTE WHICH STATES THE
 PANEL ALREADY EXISTS, YET THE PLANS STATE THE PANEL AND
 THE MAIN SERVICE IS NEW.
 WHICH IS ACCURATE?
  
  
 8) NOTE: PLEASE SEE 210.52B1 AS ALL CIRCUITS FOR DINING
 ROOM RECEPTACLES SHALL BE 20AMP AND #12. PANEL SCHEDULE
 DOES NOT DELINEATE BETWEEN LIGHTS OR RECEPTACLES. PANEL
 SCHEDULE DOES STATE AFCI PROTECTION WHICH IS NOT
 REQUIRED HOWEVER MAY BE INSTALLED.
 PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS ALL
 ADDITIONAL DEDICATED CIRCUITS ABOVE THE TWO MINIMUM
 SMALL APPLIANCE CIRCUITS SHALL BE FIGURED AT 1500VA FOR
 EACH. LOAD CALCULATIONS ONLY INDICATE TWO SMALL
 APPLIANCES FOR LOADS.
  
 9) NOTE: AS NOTED ABOVE IN COMMENTS #8, SEE 210.52B1,
 210.11C1 AND 220.53 FOR ALL SMALL APPLIANCE LOADS AND
 ANY DEDICATED DINING ROOM RECEPTACLE CIRCUITS. THE
 PANEL SCHEDULE INDICATES 3-SMALL APPLIANCE CIRCUITS
 BEFORE ADDING ANY DINING ROOMS.
  
 10) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER
 HEATERS ARE CONSIDERED CONTINUOUS LOADS. SEE NEC
 COMMENTARY AS THE LAST SENTENCE STATES WHEN SIZING FOR
 SERVICE AND FEEDERS ALSO. THIS MEANS THE WATER HEATER
 4500VA SHALL BE FIGURED AT 125% INTO LOAD CALCULATIONS.
  
 11) NOTE: PLEASE INDICATE AIC RATING FOR MAIN AND PANEL
 PER 110.9.
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  