2009-08-10 15:42:282007 FBC W/2009 REVISIONS
 LEVEL 1 ALTERATION
  
 DENIED
  
 (1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED METHODOLOGIES AS REQUIRED BY FBC R
 M1401.3. AND REQUESTED IN FIRST REVIEW COMMENTS.
  
 (2) THE TWO SETS OF MECHANICAL PLANS THAT WERE
 SUBMITTED ARE NOT ADEQUATE. IN ADDITION TO THE GRILL
 SIZES, SPECIFY THE DUCT SIZES AND CFM AT EACH SUPPLY
 GRILL ON THE PLANS. SPECIFY THE SIZE AND LOCATION OF
 THE RETURN AIR SYSTEM. PLEASE SPECIFY THE ADDRESS OF
 THE PROJECT AND THE PERSON RESPONSIBLE FOR THE DESIGN
 ON THE PLANS. SEE FBC R M1601 AND N1110.AB.1 OF THE
 2007 ENERGY GLITCH AMENDMENTS.
  