| Plan Review Notes For Permit 09060429 |
| Permit Number |
09060429 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-08-10 15:42:28 | 2007 FBC W/2009 REVISIONS | | | LEVEL 1 ALTERATION | | | | | | DENIED | | | | | | (1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS IN ACCORDANCE WITH ACCA MANUAL J OR | | | OTHER APPROVED METHODOLOGIES AS REQUIRED BY FBC R | | | M1401.3. AND REQUESTED IN FIRST REVIEW COMMENTS. | | | | | | (2) THE TWO SETS OF MECHANICAL PLANS THAT WERE | | | SUBMITTED ARE NOT ADEQUATE. IN ADDITION TO THE GRILL | | | SIZES, SPECIFY THE DUCT SIZES AND CFM AT EACH SUPPLY | | | GRILL ON THE PLANS. SPECIFY THE SIZE AND LOCATION OF | | | THE RETURN AIR SYSTEM. PLEASE SPECIFY THE ADDRESS OF | | | THE PROJECT AND THE PERSON RESPONSIBLE FOR THE DESIGN | | | ON THE PLANS. SEE FBC R M1601 AND N1110.AB.1 OF THE | | | 2007 ENERGY GLITCH AMENDMENTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|