Plan Review Notes
Plan Review Notes For Permit 09060428
Permit Number 09060428
Review Stop E
Sequence Number 3
Notes
Date Text
2009-09-22 16:47:23 
  
  
 ** DENIED **
  
 ** NEW PLANS NOW SUBMITTED FOR THE FIRST TIME FOR
 REVIEW. PREVIOUS REVIEWS DID NOT CONTAIN ANY ELECTRICAL
 PLANS. THE PREVIOUS REVIEW NOTE BY PREVIOUS ELECTRICAL
 REVIEWER HAD TO DO WITH *ELECTRICAL SERVICE CHANGE*
 PERMIT ONLY.
  
  
  
 1) NOTE: PLANS CONTAIN A NOTE ON COVER SHEET WHICH
 STATES ALL ELECTRICAL IS TO BE DONE UNDER THE 2008 NEC.
 HOWEVER ALL PERMIT APPLICATIONS SUBMITTED BEFORE
 OCTOBER 1ST, 2009 ARE UNDER THE 2005 NEC.
  
 2) NOTE: PLEASE SEE 210.52D FOR GFI RECEPTACLE TO BE
 LOCATED WITHIN 3FT OF THE MASTER BEDROOM SINK.
  
 3) NOTE: PLEASE SEE FBC R313.1,313.2, 313.2.1 FOR SMOKE
 ALARMS WHICH ARE REQUIRED TO BE BROUGHT UP TO CURRENT
 CODE. PLEASE SEE NFPA-72 11.5.1 AND 11.8.3 FOR REQUIRED
 LOCATIONS.
 PLEASE BE SURE TO SEE 11.8.3 AS ALL SMOKE ALARMS WITHIN
 20FT OF COOKING APPLIANCES SHALL MEET SPECIFIC
 REQUIREMENTS. ( OUTSIDE MASTER BEDROOM)
  
 4) NOTE: PLANS ONLY INDICATE ONE A/C SYSTEM YET THE
 PANEL SCHEDULE INDICATES TWO ADDITIONAL MINI-SPLIT
 SYSTEMS HOWEVER THE ELECTRICAL AND MECHANICAL PLANS DO
 SHOW EITHER OF THESE TWO SYSTEMS.
 PLEASE SHOW AND SHOW DISCONNECTS PER 440.11,440.12, AND
 COMPLIANCE WITH 210.63
  
 5) NOTE: PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT
 PROTECTION FRO AHU. PANEL SCHEDULE INDICATES 50AMP FEED
 WITH #8 AWG. BOTH ARE TOO SMALL.
 MINIMUM IS 125%.
  
 6) NOTE: PLANS INDICATE BOTH DISCONNECTS AND
 RECEPTACLES PER SYMBOL LEGEND NEXT TO THE DRYER,
 OVEN/RANGE AND OTHER LOCATIONS SUCH AS AHU, WATER
 HEATER, CU ETC.
 THERE IS EQUIPMENT AND APPLIANCES IN THE NEC WHICH DO
 REQUIRE DISCONNECTING MEANS HOWEVER OTHER LOCATIONS FOR
 CORD AND PLUG EQUIPMENT WHICH COMES THAT WAY FROM THE
 MANUFACTURE AND IS LISTED AS CORD AND PLUG CONNECTED
 DOES NOT REQUIRE AND ADDITIONAL DISCONNECTING MEANS.
 THERE IS NO VIOLATION TO HAVE A DISCONNECT AND
 RECEPTACLES HOWEVER IF SHOWN THEN THEY MUST BE
 INSTALLED. IN EITHER CASE THE DISCONNECT NOTED ON PLANS
 FOR AHU IS SHOWN TOO SMALL AS NOTED IN COMMENT #5
 ABOVE.
 PLEASE ALSO SEE 110.26 FOR MINIMUM CLEARANCES.
  
 7) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING.
 BEDROOM #3 MISSING RECEPTACLE WITHIN 6FT OF DOOR.
  
 8) NOTE: PLEASE SEE 210.52B1 AS ALL CIRCUITS FOR DINING
 ROOM RECEPTACLES SHALL BE 20AMP AND #12. PANEL SCHEDULE
 DOES NOT DELINEATE BETWEEN LIGHTS OR RECEPTACLES. PANEL
 SCHEDULE DOES STATE AFCI PROTECTION WHICH IS NOT
 REQUIRED HOWEVER MAY BE INSTALLED.
 PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS ALL
 ADDITIONAL DEDICATED CIRCUITS ABOVE THE TWO MINIMUM
 SMALL APPLIANCE CIRCUITS SHALL BE FIGURED AT 1500VA FOR
 EACH. LOAD CALCULATIONS ONLY INDICATE TWO SMALL
 APPLIANCES FOR LOADS.
  
 9) NOTE: AS NOTED ABOVE IN COMMENTS #8, SEE 210.52B1,
 210.11C1 AND 220.53 FOR ALL SMALL APPLIANCE LOADS AND
 ANY DEDICATED DINING ROOM RECEPTACLE CIRCUITS. THE
 PANEL SCHEDULE INDICATES 3-SMALL APPLIANCE CIRCUITS
 BEFORE ADDING ANY DINING ROOMS.
  
 10) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER
 HEATERS ARE CONSIDERED CONTINUOUS LOADS. SEE NEC
 COMMENTARY AS THE LAST SENTENCE STATES WHEN SIZING FOR
 SERVICE AND FEEDERS ALSO. THIS MEANS THE WATER HEATER
 4500VA SHALL BE FIGURED AT 125% INTO LOAD CALCULATIONS.
  
 11) NOTE: PLEASE SHOW LOCATION AND ELECTRICAL FOR THE
 SPRINKLER PUMP/SYSTEM AS LISTED ON PANEL SCHEDULE.
 NO REVIEW FOR CODE COMPLIANCE CAN BE DONE AS THE
 LOCATION IS NOT SHOWN. PLEASE REMEMBER TO SEE 430.102
 FOR REQUIRED DISCONNECTING MEANS.
  
  
 ** AS ELECTRICAL ON SHEET IS MISSING SOME INFORMATION,
 THERE MAY BE SOME ITEMS NOT YET SUBMITTED WHICH MAY
 CREATE CODE COMMENTS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  