| Plan Review Notes For Permit 09060428 |
| Permit Number |
09060428 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-09-16 16:15:45 | 2007 FBC W/2009 REVISIONS | | | LEVEL 2 ALTERATION | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE | | | STRUCTURAL WINDOW MULLIONS AS REQUIRED BY DCA RULE | | | 9B-72. | | | | | | 2) SUBMIT TWO SETS OF REVISED ENERGY CALCULATIONS, WITH | | | 47.9 K BTU COOLING SYSTEM AS SHOWN ON THE MECHANICAL | | | PLANS AND LOAD CALCS. | | | | | | 3) CLARIFY THE EXTERIOR DOOR THAT WILL BE USED AND | | | SUBMIT TWO COMPLETE SETS OF PRODUCT APPROVALS. THE FL | | | COVER SHEET SUBMITTED IS FOR A STEEL DOOR WITH WOOD | | | FRAME AND THE NOA ATTACHED TO IT IS FOR A STEEL DOOR | | | WITH A METAL FRAME. | | | | | | 4) THE PROJECT IS A LEVEL 2 ALTERATION PER THE EXISTING | | | BUILDING CODE. PLEASE REVISE SHEET 1.2. | | | | | | 5) SPECIFY THE LOCATION OF THE SMOKE DETECTORS ON THE | | | PLANS AS REQUIRED BY FBC R313.2.1. | | | | | | 6) ON SHEET 2.2 THE EXPOSURE CATEGORY IS SPECIFIED AS B | | | UNDER DESIGN PARAMETERS AND AS EXPOSURE C UNDER | | | STRUCTURAL NOTES. PLEASE CORRECT AND COORDINATE THE | | | COMPONENT AND CLADDING PRESSURES WITH THE APPROPRIATE | | | EXPOSURE CATEGORY. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|