| Plan Review Notes For Permit 09060428 |
| Permit Number |
09060428 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-08-10 11:00:26 | 2007 FBC | | | RENOVATION | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF A KEY PLAN FOR THE ACCORDION | | | SHUTTERS. THE NUMBERING OF THE OPENINGS ON THE KEY PLAN | | | SHALL CORRESPOND TO THE THE OPENING NUMBERS ON THE | | | INSTALLATION SCHEDULE. PREVIOUS COMMENT THAT HAS NOT | | | BEEN ADDRESSED. THE OPENING NUMBER/LETTER | | | IDENTIFICATION MARKS ON THE KEY PLAN, THAT WAS | | | SUBMITTED, DOES NOT MATCH THE INSTALLATION SCHEDULE. | | | | | | 2) SPECIFY WINDOW OPENING SIZES, CONFIGURATIONS, NUMBER | | | OF ANCHORS, SILL TYPE, GLASS TYPE AND DESIGN PRESSURES | | | FOR THE HORIZONTAL SLIDING WINDOWS THAT WILL BE | | | INSTALLED. CIRCLE THE APPROPRIATE ITEMS ON THE TABLES | | | GIVEN IN THE NOA. PREVIOUS COMMENT THAT HAS NOT BEEN | | | ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|