| Plan Review Notes For Permit 09060428 |
| Permit Number |
09060428 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-07-10 16:25:45 | 2007 FBC | | | RENOVATION | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF A KEY PLAN FOR THE ACCORDION | | | SHUTTERS. THE NUMBERING OF THE OPENINGS ON THE KEY PLAN | | | SHALL CORRESPOND TO THE THE OPENING NUMBERS ON THE | | | INSTALLATION SCHEDULE. | | | | | | 2) THE EDGE DISTANCE IS REQUIRED TO BE 3-1/2" IN ORDER | | | TO USE THE ANCHOR SPACING IN THE TABLES OF THE | | | ACCORDION SHUTTER NOA. SEE PAGE 11 OF THE DRAWINGS. | | | | | | 3) SPECIFY WINDOW OPENING SIZES, CONFIGURATIONS, NUMBER | | | OF ANCHORS, SILL TYPE, GLASS TYPE AND DESIGN PRESSURES | | | FOR THE HORIZONTAL SLIDING WINDOWS THAT WILL BE | | | INSTALLED. CIRCLE THE APPROPRIATE ITEMS ON THE TABLES | | | GIVEN IN THE NOA. | | | | | | 4) SHOW THAT THE SLEEPING ROOM WINDOWS WILL COMPLY WITH | | | FBC R310 AND SECTION 604 OF THE EXISTING BUILDING CODE | | | FOR EMERGENCY ESCAPE AND RESCUE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|