Plan Review Notes
Plan Review Notes For Permit 09060427
Permit Number 09060427
Review Stop M
Sequence Number 1
Notes
Date Text
2009-06-30 19:37:10MECHANICAL PLAN REVIEW 06/30/09
  
 1. PLEASE PROVIDE PLANS SIGNED BY AN APPROPRIATELY
 QUALIFIED PERSON, ABLE TO DESIGN THE MECHANICAL SYSTEM
 BEING PERMITTED. THESE PLANS APPEAR TO BE SHOP DRAWINGS
 AND BEAR NEITHER THE SIGNATURE OF THE MECHANICAL
 CONTRACTOR OR A QUALFIED DESIGN PROFESSIONAL AS WELL AS
 NO LICENSE NUMBERS (FBC106.1, FS471, FS481).
 2. NO INFORMATION ON THE GREASE DUCT APPEARS TO HAVE
 BEEN PROVIDED BETWEEN THE HOOD ITSELF AND THE ROOFTOP
 FAN. PLEASE PROVIDE DETAILS AND ENSURE PROPER
 CLEARANCES TO COMBUSTIBLE BUILDING COMPONENTS
 (FBC106.1.1, FMC507.9).
 3. PLEASE PROVIDE A PARTIAL FLOOR PLAN WHICH INDICATES
 WHERE THE HOOD IS BEING LOCATED WITHIN THE DELI AND
 PLEASE INCLUDE THE PROPOSED LOCATION OF THE MANUAL PULL
 STATION. NOTE: THE MANUAL PULL STATION MUST BE LOCATED
 IN THE NATURAL PATH OF EGRESS AWAY FROM THE HOOD A
 MINIMUM OF 10' AND A MAXIMUM 20' FROM THE PROPOSED
 GREASE HOOD (FBC904.11.1).
 4. PLEASE SPECIFY HOW MAKEUP AIR IS BEING PROVIDED TO
 THE GREASE HOOD (FMC508.1).
 5. PLEASE PROVIDE A STATEMENT FROM A QUALIFIED DESIGN
 PROFESSIONAL INDICATING HOW THE PROPOSED ROOFTOP
 MECHANICAL EQUPMENT (FAN) IS BE SECURED AND THAT SAID
 EQUIPMENT WILL ITSELF WITHSTAND THE WIND FORCES
 ANTICIPATED AT THE INTENDED LOCATION (FBC1609).
 6. THE FAIR MARKET VALUE OF THIS IMPROVEMENT APPEARS TO
 HAVE BEEN UNDERESTIMATED. PLEASE PROVIDE A FAIR MARKET
 VALUE ESTIMATE WHICH INCLUDES THE VALUE OF BOTH
 INSTALLATION AND THE EQUIPMENT BEING PROVIDED BY THE
 BUILDING OWNER AS WELL AS ANY OVERHEAD AND PROFIT ON
 THE PROJECT.
  
 PLEASE FEEL FREE TO CONTACT ME DIRECTLY AT 561-805-6650
 IF YOU HAVE ANY QUESTIONS ABOUT THE SPECIFIC
 DEFICIENCIES IDENTIFIED DURING THIS REVIEW.
  