| 2009-06-30 19:37:10 | MECHANICAL PLAN REVIEW 06/30/09 |
| | |
| | 1. PLEASE PROVIDE PLANS SIGNED BY AN APPROPRIATELY |
| | QUALIFIED PERSON, ABLE TO DESIGN THE MECHANICAL SYSTEM |
| | BEING PERMITTED. THESE PLANS APPEAR TO BE SHOP DRAWINGS |
| | AND BEAR NEITHER THE SIGNATURE OF THE MECHANICAL |
| | CONTRACTOR OR A QUALFIED DESIGN PROFESSIONAL AS WELL AS |
| | NO LICENSE NUMBERS (FBC106.1, FS471, FS481). |
| | 2. NO INFORMATION ON THE GREASE DUCT APPEARS TO HAVE |
| | BEEN PROVIDED BETWEEN THE HOOD ITSELF AND THE ROOFTOP |
| | FAN. PLEASE PROVIDE DETAILS AND ENSURE PROPER |
| | CLEARANCES TO COMBUSTIBLE BUILDING COMPONENTS |
| | (FBC106.1.1, FMC507.9). |
| | 3. PLEASE PROVIDE A PARTIAL FLOOR PLAN WHICH INDICATES |
| | WHERE THE HOOD IS BEING LOCATED WITHIN THE DELI AND |
| | PLEASE INCLUDE THE PROPOSED LOCATION OF THE MANUAL PULL |
| | STATION. NOTE: THE MANUAL PULL STATION MUST BE LOCATED |
| | IN THE NATURAL PATH OF EGRESS AWAY FROM THE HOOD A |
| | MINIMUM OF 10' AND A MAXIMUM 20' FROM THE PROPOSED |
| | GREASE HOOD (FBC904.11.1). |
| | 4. PLEASE SPECIFY HOW MAKEUP AIR IS BEING PROVIDED TO |
| | THE GREASE HOOD (FMC508.1). |
| | 5. PLEASE PROVIDE A STATEMENT FROM A QUALIFIED DESIGN |
| | PROFESSIONAL INDICATING HOW THE PROPOSED ROOFTOP |
| | MECHANICAL EQUPMENT (FAN) IS BE SECURED AND THAT SAID |
| | EQUIPMENT WILL ITSELF WITHSTAND THE WIND FORCES |
| | ANTICIPATED AT THE INTENDED LOCATION (FBC1609). |
| | 6. THE FAIR MARKET VALUE OF THIS IMPROVEMENT APPEARS TO |
| | HAVE BEEN UNDERESTIMATED. PLEASE PROVIDE A FAIR MARKET |
| | VALUE ESTIMATE WHICH INCLUDES THE VALUE OF BOTH |
| | INSTALLATION AND THE EQUIPMENT BEING PROVIDED BY THE |
| | BUILDING OWNER AS WELL AS ANY OVERHEAD AND PROFIT ON |
| | THE PROJECT. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME DIRECTLY AT 561-805-6650 |
| | IF YOU HAVE ANY QUESTIONS ABOUT THE SPECIFIC |
| | DEFICIENCIES IDENTIFIED DURING THIS REVIEW. |
| | |
| | THANK YOU, |
| | |
| | DOUG WISE - PX1276 |