Plan Review Notes
Plan Review Notes For Permit 09060420
Permit Number 09060420
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-04 15:05:25 
 ** DENIED PLANS REVIEW **
  
 1) NOTE: PLANS SUBMITTED NEED TO SHOW MINIMUM
 SUFFICIENT CODES AND ELECTRICAL DETAILS PER FBC 2007
 AND NEC 2005.
 PLANS SUBMITTED ARE NOT SUFFICIENT FOR CLARITY,
 INFORMATION OR MINIMUM DESIGNS.
 PLEASE SEE NEC 250,600 FOR SOME OF THE MINIMUMS. FBC
 106.1.1,106.1.2,106.5 FOR CLARITY, COORDINATION,
 DETAILS OF RECORD PLANS.
 PLANS NEED TO STATE THE FOLLOWING CODES FOR THE
 RELEVANT SCOPE OF WORK.
 2005 NFPA-70
 ** PLANS STATE THE 2008 NEC, HOWEVER THE STATE OF
 FLORIDA TO DATE HAS NOT ADOPTED THE NEW VERSION OF THE
 NEC.
  
 2) NOTE: THE VALUE FOR THE APPLIED SCOPE OF WORK NEEDS
 TO BE UPDATED. THE APPLIED VALUE FOR THE SIGN IS
 EXTREMELY LOW. IF AN APPROPRIATE VALUE IS NOT ADJUSTED
 ONE WILL BE ADJUSTED USING THE ADOPTED GUIDES UNDER FBC
 108.3.
 LED LIGHTING KITS FOR SIGNS IS SUBSTANTIAL.
 IT IS NOT POSSIBLE TO DESIGN, BUILD, INSTALL AND WIRE
 THE SIGNS SHOWN ON PLANS FOR THE APPLIED VALUE OF
 $1500.00. THE VALUE IS TO INCLUDE ANY ITEMS EVEN IF
 OWNER SUPPLIED.
  
 3) NOTE: PLEASE SHOW DISCONNECTS PER 600.5.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  