| Plan Review Notes For Permit 09060411 |
| Permit Number |
09060411 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-16 16:25:45 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- ACCORDING TO APPROVED ASSEMBLIES ON SHEET 3 OF | | | UNDERLAYMENT NOA 07-1130.01 SUBMITTED THIS UNDERLAYMENT | | | CAN ONLY BE USED WHEN THE APPROVED ROOFING ASSEMBLY | | | ALLOWS AN ASTM D 1970 UNDERLAYMENT. ROOFING ASSEMBLY | | | SUBMITTED DOESN'T ALLOW THIS TYPE OF UNDERLAYMENT. | | | PROVIDE UNDERLAYMENT PRODUCT APPROVAL THAT IS ALLOWED | | | BY THE ROOFING ASSEMBLY SUBMITTED. | | | | | | 2- LIMITATION #6 ON SHEET 4 OF UNDERLAYMENT NOA | | | 07-1130.01 SUBMITTED STATES THAT MAXIMUM ROOF PITCH IS | | | 4:12. PERMIT APPLICATION STATES 9:12 PITCH. THIS | | | UNDERLAYMENT DOESN'T WORK FOR PROPOSED INSTALLATION. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|