| Plan Review Notes For Permit 09060398 |
| Permit Number |
09060398 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-17 09:20:17 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | | AT | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | PLEASE CLARIFY THE FOLLOWING ISSUES: | | | | | | "CONCRETE" IS CIRCLED ON PAGE 2 OF THE PRODUCT | | | APPROVAL. IF THIS IS INSTALLED HORIZONTALLY, HOW HAVE | | | YOU DETERMINED THAT THE COLUMNS ARE FORMED AND POURED | | | COLUMNS RATHER THAN FILLED BLOCK? | | | | | | THE ENTIRE LINE WAS CIRCLED ON THE PRODUCT APPROVAL, | | | BUT 2' OC ANCHOR SPACING DOES NOT COMPLY WITH THE | | | DESIGN PRESSURE YOU HAVE SPECIFIED ON THE ENGINEERING. | | | | | | | | | |
|