| 2009-06-15 14:46:53 | RE-ROOF BUILDING REVIEW CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- REVISE RAS 117 CALCULATIONS FOR FLAT ROOF SYSTEM: |
| | A) ENGINEER TO REVISE DESIGN PRESSURES. THIS BUILDING |
| | IS LOCATED ON EXPOSURE "C" NOT "B". |
| | |
| | B) REVISE NAIL ENHANCING AT PERIMETER AND CORNER AREAS. |
| | COORDINATE WITH ITEM 1A ABOVE. |
| | |
| | 2- CLARIFY HOW ARE REPAIRS (COATING) GOING TO BE DONE |
| | ON FLAT ROOF SHOWN ON SKETCH ON SHEET 5 SUBMITTED. IS |
| | THIS A ROOF OVER?. PROVIDE CORRESPONDING PRODUCT |
| | APPROVAL FOR RECOVERY OR ROOF OVER APPLICATIONS. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL FOR: |
| | A) SELF-ADHERED UNDERLAYMENTS TO BE ISSUED. |
| | |
| | B) POLYFOAM TO BE USED IN CONCRETE TILE. SEE TILE |
| | PRODUCT APPROVAL FOR LISTED TYPES. |
| | |
| | C) ROOF TILE. FLORIDA PRODUCT APPROVAL FL601-R3 |
| | SUBMITTED IS MISSING THE NOA 07-0711.03 THAT WAS |
| | SUBMITTED TO GET THE FLORIDA PRODUCT APPROVAL. |
| | |
| | D) COPPER PANELS THAT RESIST THE UPLIFT PRESSURES |
| | CALCULATED FOR ROOF ZONE 2 AND ROOF ZONE 3. NOA |
| | 07-0822.05 SUBMITTED IS GOOD FOR MAX. DESIGN PRESSURE |
| | OF -76.75PSF. RATIONAL ANALYSIS IS NOT ALLOWED. SEE |
| | SYSTEM LIMITATION #1 ON SHEET 4 OF NOA SUBMITTED. |
| | (NOTE: SAME COMMENT APPLIES TO FLORIDA PRODUCT APPROVAL |
| | FL10601-R2 SUBMITTED). |
| | ***NOTE: THIS BUILDING IS LOCATED ON EXPOSURE "C". |
| | THEREFORE DESIGN PRESSURES ARE HIGHER THAN THOSE SHOWN |
| | ON THIS PRODUCT APPROVAL. |
| | |
| | 4- SEPARATE PERMIT FOR A/C ROOF TOP UNITS IS REQUIRED |
| | TO COMPLY WITH SEC. 301.12 OF 2007 FLORIDA MECHANICAL |
| | CODE. SLEEPERS ARE NOT ALLOWED. COORDINATE WITH HAROLD |
| | MOSER (561)805-6732. |
| | |