| 2009-07-05 14:07:09 | |
| | ** DENIED PLANS REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES NEED TO BE |
| | UPDATED. THE COVER SHEET DOES LIST MOST OF THE CURRENT |
| | ADOPTED CODES HOWEVER NOT ALL. |
| | PLEASE SEE THE FOLLOWING. |
| | |
| | 2006 NFPA-101. THIS EDITION WAS ADOPTED DECEMBER 31ST |
| | 2008. FAC 69A-60.004 |
| | 2007 FLORIDA FIRE PREVENTION CODE. |
| | |
| | ALL PLANS SHALL CONTAIN MINIMUM DESIGN CODES. |
| | |
| | 2) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS SHOWING |
| | MINIMUM CODE COMPLIANCE. PLEASE COORDINATE WITH PANEL |
| | SCHEDULES TO BE SUBMITTED. |
| | THERE ARE NUMEROUS ITEMS FOR MINIMUM CODE COMPLIANCE |
| | WHICH CAN NOT BE REVIEWED AT THIS TIME. |
| | 408.4,310.16,240,220 ETC PLEASE BE SURE TO CIRCUIT |
| | EMERGENCY AND EXIT LIGHTS PER 700.12F |
| | |
| | EVERYTHING IS SHOWN AS NEW. PLEASE PLACE ITEMS ABOVE ON |
| | PLANS. THE PLANS STATES MANY ITEMS ARE NO CLEAR ON |
| | PANELS YET LOADS FOR NEW CIRCUITS, RECEPTACLES ETC |
| | SHOULD BE KNOWN AT THIS TIME. |
| | THE PLANS ALSO STATE THE *ENTIRE* 8TH FLOOR IS FED FROM |
| | ONE 125AMP PANEL. IF THIS IS THE CASE THERE IS CONCERN |
| | ON LOADS ON EQUIPMENT. PLANS SHOW THREE SEPARATE PANELS |
| | ??? |
| | ** ALL TENANTS ARE FED FROM ONE METER? |
| | |
| | |
| | 4) NOTE: PLEASE SEE 13-415.AB.5 FOR MINIMUM CODE |
| | COMPLIANCE REQUIRED FOR LIGHTING PERFORMANCE |
| | CALCULATIONS. |
| | ** PLEASE BE SURE TO COMPLETE A FIXTURE LEGEND WHICH |
| | STATES THE SPECIFIC FIXTURES. |
| | |
| | |
| | *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE |
| | PERMITS. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |