| 2009-08-05 14:04:27 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | |
| | |
| | 1. SEE COMMENTS 1, 1A & 1B BY THE BUILDING PLANS |
| | REVIEWER AND COMMENT 2 BY THE ELECTRICAL PLANS |
| | REVIEWER. THESE COMMENTS SHALL BE ADDRESSED PRIOR TO |
| | PERMIT ISSUANCE. |
| | |
| | 2. SHT P-102 NOTE STATES IN PART "CONNECT NEW 4" |
| | SANITARY LINE" BUT SHOWS A 6" SANITARY LINE. PLEASE |
| | CLARIFY. SECTIONS 106.1.1 & 701.1. |
| | |
| | 3. SHT P-103 SANITARY RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN WHERE THE FLOOR DRAIN CONNECTS TO THE |
| | BRANCH LINE WEST OF THE BOUTIQUE. THE FLOOR PLAN SHOWS |
| | THE FLOOR DRAIN IN THE DOG ADOPTION ROOM CONNECTING |
| | BETWEEN THE 2ND AND THIRD FLOOR DRAINS TO THE EAST OF |
| | THE BRANCH LINE, BUT BETWEEN THE 1ST & 2ND FLOOR DRAINS |
| | ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTIONS |
| | 106.1.1 & 701.1. |
| | |
| | 4. SHT P-203 A SHUT OFF VALVE IS REQUIRED ON THE WATER |
| | SUPPLY LINE TO EACH HOSE BIBB. SECTION 606.2(2). |
| | |
| | 5. SHT P-300 PLUMBING NOTES NUMBER 13. AIR CHAMBERS ARE |
| | NOT APPROVED. PDI-WH 201. PLEASE DELETE FROM NOTES. |
| | |
| | ***NOTE: THE COMMENTS 3 THRU 5 CAN BE PROVISO'D AND |
| | REVISIONS CAN BE SUBMITTED FOR THESE COMMENTS.*** |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |