| Plan Review Notes For Permit 09060303 |
| Permit Number |
09060303 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-07-21 08:38:13 | GRACE PAVILLION | | | 3100 NORTH MILITARY TRAIL | | | PHASE II, INCLUDING HVAC UNITS, PLUMBING, AND FLAT WORK | | | | | | 1. WRONG CODE REFERENCES NOTED ON PAGE CS-1. | | | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER SYSTEM REMODEL. | | | | | | 3. ALL REQUIRED FIRE DAMPERS ARE TO BE DROP TESTED | | | AFTER INSTALLATION. | | | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | | ALARM SYSTEM REMODEL OR ADDITIONS. | | | | | | 5. PLANS DO NOT ILLUSTRATE ILLUMINATED EXIT SIGNS OR | | | PORTABLE FIRE EXTINGUISHER LOCATIONS. | | | | | | 6. TWO HOUR RATED WALLS ARE DISPLAYED BUT COULD NOT | | | LOCATE RATED DOOR INFORMATION. | | | | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|