| 2009-07-05 10:15:19 | REVIEW FOR ELECTRICAL COMPLETED AND PLANS ROUTED BACK |
| | TO ENG AS THEY WERE SIGNED OUT. |
| 2009-07-05 10:14:04 | |
| | ** DENIED PLANS REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING MINIMUM CODES ARE |
| | STATED ON PLANS AS THEY ARE RELEVANT FOR THE MINIMUM |
| | DESIGNS. THERE IS CONFLICTS ON THE COVER SHEET FOR |
| | EXAMPLE WHICH INDICATES BOTH THE 2002 AND 2005 NEC. |
| | ALSO INDICATES 2003 NFPA-101 |
| | AFTER DECEMBER 8TH, 2006 THE STATE OF FLORIDA ADOPTED |
| | THE 2005 NEC. |
| | AFTER DECEMBER 31ST, 2008 THE STATE OF FLORIDA UNDER |
| | FAC 69A-60.004, AND 69A-3.012 ADOPTED THE 2006 NFPA-101 |
| | THE PLANS INDICATE THE 2004 FLORIDA FIRE PREVENTION |
| | CODE HOWEVER UNDER THE SAME SECTIONS NOTED ABOVE THE |
| | EDITION SHOULD READ 2007. |
| | CURRENT NFPA-1 IS 2006. |
| | |
| | 2007 FBC W/ 2009 SUPPLEMENTS |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | 2007 FLORIDA FIRE PREVENTION CODE |
| | 2006 NFPA-1 |
| | |
| | |
| | 2) NOTE: THE APPLIED SCOPE OF WORK IS IN DIRECT |
| | CONFLICT WITH WORK AND AREAS UNDER THE PHASE 1 PROJECT |
| | WHICH IS UNDER A SEPARATE DESIGN TEAM. ALL PLAN SHALL |
| | BE *SHOP DRAWING REVIEW STAMPED* BY THE BASE BUILDING |
| | DESIGNERS OF RECORD. THERE IS WORK SHOWN ON THE BASE |
| | BUILDING DESIGN TEAMS PLANS WHICH IS ALSO IN THESE SAME |
| | AREAS. |
| | UNTIL THE BASE BUILDING AND THOSE AREAS ARE CLOSED FOR |
| | FINAL SCOPE OF WORK AND CONTAIN A CERTIFICATE OF |
| | OCCUPANCY THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE |
| | FOR THE SCOPE OF WORK. |
| | |
| | *** DO NOT SUBMIT REVISIONS TO BASE BUILDING UNDER THE |
| | SUBMITTED PERMITTED FOR NEW SCOPE OF WORK. |
| | |
| | THE BASE BUILDING PLANS HAVE NOT BEEN REVISED TO REMOVE |
| | SCOPE OF WORK FROM THEIR PLANS. MANY OF THESE LOCATIONS |
| | ARE REQUIRED TO CONTAIN MINIMUM LIFE SAFETY BEFORE C OF |
| | O CAN BE GRANTED. |
| | |
| | ** THERE IS STILL A FEE DUE HOLD ALSO ON BASE BUILDING |
| | BEFORE C OF O. THE AMOUNT OF $57,200 REMAINS |
| | OUTSTANDING. |
| | |
| | |
| | 3) NOTE: PLEASE SEE FBC 13-415.AB.5 FOR REQUIRED |
| | CALCULATIONS AND COORDINATION OF ALL DOCUMENTS AND |
| | REPORTS WITH THE SUBMITTED PLANS. THERE ARE |
| | INCONSISTENCIES IN THE SUBMITTED PLANS AND |
| | CALCULATIONS. |
| | |
| | A) PLEASE EXPLAIN THE INPUT DATA REPORT WHICH DOES NOT |
| | COORDINATE WITH PLANS. SEE COMMENTS FROM OTHER TRADES |
| | AS FOR EXAMPLE, THE WAREHOUSE/STORAGE/KENNEL AREAS |
| | INDICATE FLOORS AS *CARPET AND RUBBER PADDING*. THIS IS |
| | NOT POSSIBLE. |
| | |
| | B) SCOPE OF WORK ACTUAL SQUARE FOOTAGE NEEDS TO |
| | COORDINATE FROM PLANS TO THE SUBMITTED CALCULATIONS. |
| | |
| | C) SEE THE IDR AS THE LIGHTING CONTROLS ARE SHOWN AS |
| | MANUAL ON/OFF. NOT ALL AREAS ARE MANUAL ON/OFF WHERE |
| | WORK IS ACTUALLY BEING DONE. |
| | |
| | D) SEE THE LPD ON PLANS WHICH IS LESS THAN THAT |
| | SUBMITTED AND SHOWN ON THE INPUT DATA REPORT AND |
| | SUMMARY SHEETS OF THE SUBMITTED FLA COM REPORT. PLEASE |
| | EXPLAIN CONFLICT. |
| | |
| | E) PLEASE SEE THE IDR AS *ALL* FIXTURES ARE SHOWN AS |
| | 64WATT FIXTURES, YET THE PLANS CLEARLY INDICATE |
| | FIXTURES WITH A MUCH GREATER WATTAGE. |
| | PLEASE SEE 13-415.AB.5.1 AS THE VA RATING SHALL BE |
| | BASED ON THE INPUT OF THE BALLAST. DO NOT USE THE BULBS |
| | AS WATTAGE. SOMETIMES THIS CAN HELP ON CALCULATIONS |
| | DEPENDING ON THE EFFICIENCY RATING OF FIXTURES. |
| | SOMETIMES THE FIXTURE VA IS HIGHER THAN THE WATTAGE OF |
| | BULBS. |
| | |
| | 4) NOTE: PLEASE SEE FBC 11-4.27.4. AREAS IN WHICH MAY |
| | BE ACCESSIBLE TO ADA SHALL NOT CONTAIN SWITCHING |
| | DEVICES WHICH DO NOT MEET SECTION GIVEN. |
| | NOT ALL LOCATIONS WOULD BE CONSIDERED ADA HOWEVER SOME |
| | ON PLANS ARE. |
| | |
| | 5) NOTE: PLEASE PROVIDE ACCURATE PANEL SCHEDULES FROM |
| | BASE BUILDING DESIGN TEAM AND INCORPORATE INTO THE |
| | SUBMITTED PANEL SCHEDULES. THE RECORD SET OF PLANS WILL |
| | NEED TO BE ACCURATE FOR SCOPE. |
| | EXISTING CIRCUITS MAY JUST BE LABELED WITH AN *E* NEXT |
| | TO EACH ITEM ON THE OUTSIDE OF SCHEDULE. |
| | 408.4. |
| | ALL LOADS SHALL BE REVISED WITH THE LATEST PLANS OF |
| | JOBSITE ONCE CO IS ISSUED. |
| | |
| | |
| | *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE |
| | PERMITS. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |